PD testing system for XLPE cable under 220kV

Model
Nature of the Manufacturer
Manufacturer
Product Category
Partial discharge system
Place of Origin
City, Province
Overview
PD testing system for XLPE cable under 220kV
Product Details


This system is developed from the foreign advanced technology & interrelated product. It suits the test of PD detect, withstand test and PD fault locate of the XLPE cables under 220kV. The relevant recommendations: GB/T11017-2002, GB/T12706-2008 and IEC60502-2005. The whole system has the advantage of the compact structure, multi-function, easy operate and safety. It can supersede the analogously equipment of foreign production. It is composed of high voltage reactor, double shield isolation transformer, regulator, high voltage capacitive divider, high voltage injection capacitor, PD detector, PD fault locator and shielded room. The whole system more than three hundred have been using in the electric wire & cable manufactures.
1.Figure Drawing of the system

1-double isolation transformer 2-control desk 3-regulator 4-low voltage filter 5-exciter transformer 6-high voltage reactor 7-capacitive divider 8-PD detector 9- PD fault locator 10-high voltage filter 11-high voltage injection capacitor 12-test terminal of cable 13-test object
2.Main feature
●PD level:≤2Pc
● Quality facror:Q≥40
●Accuracy of fault locating:≤±2.5m(±1%)
● Accuracy of voltage measurement:≤±3%
●The system has the function of timer, ARC detector, interlock, over current protection, zero start and output tap setting control. Tuning range can work on the PD test, withstand test and fault locate of power cable of max. cross-section 400mm2 ,longest length 2000m for rated voltage under 110kV.  
3.Main feature of shield room and control room
●Resistance of ground is less than 1Ω or less than resistance of ground power distribution.(These shall be done by user according to our drawing)
●Resistance of insulating layer≥1000MΩ
●Attenuation of shield room: 10kHz-100kHz:60dB-80dB,
100kHz-100MHz:70dB-100dB
●Dimensions of the shield room suits the user’s requirement. The whole structure of the building is made of steel frames. The wall is covered with steel plate. Sandwich-structure color steel plates filled with form are used to decorate the outside wall. The control room is composed of sandwich-structure color steel plates, the window and door is made of aluminum alloy. The floor covered with internal decoration floor plates.