Ethernet Interface
Protocol: Modbus-TCP server
Ports Number: 2 pcs (supports switching function)
Communication Rate: l0M/l00Mbps, self-adaptive
Connector: RJ45
Main Technical Parameters
Network Working Mode: Transparent transmission and address mapping are optional, Modbus TCP protocol
Network Protocol: ETHERNET,ARP,IP,TCP,ICMP
TCP Connection: Max. 5 pcs
Supports Slave: Max. 62pcs (no relay)
Mapping Mode Protocol Function Code: 0x01,0x02,0x03,0x04,0x05,0x06,0x0F, 0x10
Modbus Data Storage Area:
0xxxx area (coil): 8192 Bit
Ixxxx area(discrete input): 8192 Bit
3xxxx area (input register): 2048 Word
4xxxx area (holding register): 2048 Word
3xxxx area (system diagnosis area): 263 Word
Ordering Information
ODOT-S2E2: 2 Ports Modbus RTU/ASCII to Modbus TCP Server Gateway, Serial supports RS485,9-36V DC, -40~85°C
ODOT-S4E2: 4 Ports Modbus RTU/ASCII to Modbus TCP Server Gateway, Serial supports RS485,9~36V DC, -40~85°C