UV Dose For Inactivation UV dose (mJ/cm2): UV energy per unit area UV dose = intensity (mW/cm2) ×exposure time (s) UV dose is critical for Disinfection system For Engineering, we use minimum 40 mJ/cm2 for 4-log (99.99% )inactivation level in the system Typical Design Manual:Germany - DVGW(Drinking Supply UV Disinfection System),USA/Canada-EPA UV Disinfection Guidance.
Water Quality Requirements Water quality plays a major role in the transmission of germicidal UV rays. It is recommended that the water does not exceed following maximum concentration levels.
Iron
≤0.3ppm(0.3mg/L)
Hardness
≤7gpg(120mg/L)
Turbidity
<5NTU
Manganese
≤0.05ppm(0.05mg/L)
Suspended solids
≤10ppm(10mg/l)
UV Transmittance
≥75%
Technical Parameter
Model
Inlet/Outlet
Diameter (mm)
Length (mm)
Water Flow T/H
Total Power (W)
TW-PCUD357-L1
DN40
159
430
5
57
TW-PCUD357-L2
DN50
159
430
8
114
TW-PCUD357-L3
DN50
159
430
12
171
TW-PCUD357-L4
DN65
159
430
20
228
TW-PCUD843-L1
DN65
159
910
15
172
TW-PCUD843-L2
DN80
159
910
25
344
TW-PCUD843-L3
DN100
159
910
40
516
TW-PCUD843-L4
DN100
219
910
55
688
TW-PCUD843-L5
DN125
219
910
65
860
TW-PCUD843-L6
DN125
219
910
80
1032
TW-PCUD843-L7
DN150
273
910
95
1204
TW-PCUD843-L8
DN150
273
910
110
1376
TW-PCUD1554-L1
DN100
159
1720
35
320
TW-PCUD1554-L2
DN125
219
1720
75
640
TW-PCUD1554-L3
DN150
219
1720
110
960
TW-PCUD1554-L4
DN150
219
1720
145
1280
TW-PCUD1554-L5
DN150 &DN200
273
1720
180
1600
TW-PCUD1554-L6
DN200
273
1720
220
1920
TW-PCUD1554-L7
DN200
323
1720
260
2240
TW-PCUD1554-L8
DN200 &DN250
323
1720
290
2560
Features / Benefits 1)Reasonable structure, external distribution box, can be placed in separate space and cavity separation operation; 2)Beautiful appearance and durable, the whole machine is made of 304/316/316L (optional) stainless steel material, polished inside and outside, with corrosion resistance and deformation resistance; 3)The equipment withstand voltage of 0.6MPa, protection grade IP68, UV zero leakage, safe and reliable; 4)Configure high-transmission pure quartz tube, use imported UV lamp from Toshiba Japan, the service life of the lamp exceeds 12000 hours, the UV-C attenuation is low and the output is constant during the lifetime; 5)Optional advanced online monitoring instruments and remote control systems; 6)Optional mechanical manual cleaning or automatic cleaning device to maintain efficient UV sterilization efficiency.