| Name | IVC2L |
| I/O | Digital I/O point | 20 inputs/12 outputs 32 inputs/32 outputs |
| Logic max I/O point | 512 |
| Max special module number | 8 |
| Highs peed pulse output | IVC2L:2×100kHz (only suitable for transistor output type) |
| 1PH counting channel | IVC2L:2×50kHz+4×10kHz |
| 2PH counting channel | IVC2L:1×30kHz+1×5kHz |
| Max value of the total sum of high speed counter frequency | IVC2L:80kHz |
| Digital filter function | X0~X17 adopt digital filter, input filter constant range: 0~60ms |
| Max relay output current | Resistor load | 2A/1点;8A/4 point group command terminal;8A/8 point groupcommon terminal |
| Inductive load | 220Vac, 80VA |
| Light load | 220Vac, 100W |
| Max current of transistor outptu point | Resistor load | High speed output point:0.3A/1 point;others:0.3A/1 point;0.8A/4 points;1.6A/8points The total current increases by 0.1A for eevery additional 1 point above 8points. |
| Inductive load | High speed output point:7.2W/24Vdc;others:12W/24Vdc |
| Light load | High speed output point:0.9W/24Vdc;others:1.5W/24Vdc |
| Storage | User program | 12k tep (24kByte) |
| Permannet maintenance after power off | Yes |
| Max number of component maintained at power off | Set by user (for C compoennt, the max number is 200) |
| Hardware support and maintenance time | Backup battery, maintain for three years |
| Soft component resource | Timer | 100ms precision:T0~T209 10ms precision:T210~T251 1ms precision:T252~T255 |
| Counter | 16-bit up counter:C0~C199 32-bit up down counter:C200~C235 32-bit high speed counter:C236~C255 |
| Data register | D0~D7999 |
| Local data register | V0~V63 |
| Indexed addressing register | Z0~Z15 |
| Special data register | SD0~SD255 |
| Auxiliary relay | M0~M1999 |
| Local auxiliary relay | LM0~LM63 |
| Special auxiliary relay | SM0~SM255 |
| State relay | S0~ S991 |
| Interruption resources | Internal timing interruption | 3 |
| External interruption | 16 |
| High speed counter interruption | 6 |
| Serial interruption | 12 |
| PTO output completion interruption | 2 |
| Power loss interruption | 1 |
| Regular | Basic command running time | 0.09μS |
| Real-time clock | Support |
| Analog potentiomenter | 2/8-bit precision |
| Communication | Communication port | PORT0:RS232 PORT1:RS232/RS485 |
| Communication protocol | Modbus/free port N:N/program port protocol |
| Encryption measure | Set password type | Upload password, download password, monitor password, sub-program password, formatting prohibited |
| Upload prohibited | Support |
| Application command | Real-time clock, clockcommand | Yes |
| Date and clock comparison command | Yes |
| Floating point number command | Yes |
| Positioning command | Yes |
| High speed IO command | Yes |
| MODBUS and inverter command | Yes |
| EEPROM RW command | Yes |
| Control computation command | Yes |
| Character string command | No |
| Bulk data processing command | No |
| Data sheet command | No |
| MTBF | Relay output | 200,000H (fixed to ground, mechanical stress closed to zero, with temp and RH control) |
| 100,000H (fixed to ground, mechanical stress closes to zero, without temp and RH control) |
| Transistor output | 300,000H (fixed to ground, mechanical stress closes to zero, with temp and RH control) |
| 150,000H (mechanical stress closes to zero, without temp and RH control) |
| Servicelife of outputrelay contact | 220Vac/15VA/inductive | 1sON/1s OFF, 3,200,000 times |
| 220Vac/30VA/inductive | 1s ON/1s OFF, 1,200,000 times |
| 220Vac/72VA/inductive | 1s ON/1s OFF, 300,000 times |
| Ambient environment | Rated voltage | 100~240VAC (normal operation) |
| Input voltage range | 85~264VAC (normal operation) |
| Ambient temp | -5~55℃ |
| Storage temp | -40~70℃ |
| Withstand voltage | 1 minute of 2830VAC AC or equivalent DC voltage, no breakdown or arching, leakge current ≤5mA |
| Withstand vibration | Displacement:3.5mm, acceleration:10m/s2, frequency range:5~150Hz, scan 10 times in X, Y and Z direction |
| Withstand shock | Half sine, pulse width:6ms, acceleration:180m/s2 |
| Protection level | IP20 |
| Safety certification | Design according to IEC61131-2 and UL508 standard, passCE certification |