Pin Type Insulator BS (British Standard)
P-11-Y/P-15-Y/P-22-Y/P-33-Y/P-35-Y/P-44-Y/Pw-15-Y/Pw-22-Y/Pw-33-Y
Widely used on high voltage distribution lines, Having a better anti-fog performance, can easily handle and manufacture and be mounted as necessary, vertically or horizontally.

Specification
| Pin type porcelain insulators |
| BS Class | P-11-Y | P-15-Y | P-22-Y | P-33-Y | P-44-Y | PW-15-Y | PW-22-Y | PW-33-Y |
| Creepage distance | 240 | 298 | 432 | 630 | 864 | 432 | 673 | 851 |
| Dry arcing distance | 102 | 133 | 200 | 360 | 483 | 197 | 267 | 419 |
| Main dimensions | H | mm | 133 | 137 | 165 | 244 | 318 | 185 | 255 | 320 |
| h | mm | 48 | 48 | 52.6 | 52.6 | 52.6 | 52.6 | 52.6 | 52.6 |
| D | mm | 140 | 152 | 229 | 280 | 343 | 170 | 205 | 240 |
| d | mm | 18.3 | 18.3 | 27.8 | 27.8 | 27.8 | 27.8 | 27.8 | 27.8 |
| R1 | mm | 13 | 13 | 19 | 19 | 19 | 16 | 16 | 16 |
| R2 | mm | 9.5 | 11 | 14.3 | 13 | 14.3 | 16 | 16 | 16 |
| Cantilever Strength | KN | 11 | 11 | 11 | 13 | 13 | 11 | 11 | 13 |
| Min Flashover Voltage | Power frequency | Dry | kV | 75 | 80 | 100 | 135 | 155 | 100 | 125 | 140 |
| Wet | kV | 50 | 55 | 60 | 95 | 110 | 65 | 95 | 110 |
| Critical impulse | Pos | kV | 115 | 130 | 160 | 180 | 240 | 150 | 190 | 210 |
| Neg | kV | 150 | 175 | 205 | 290 | 305 | 190 | 235 | 245 |
| Withstand voltage | One min Power Frequency | Dry | kV | 65 | 70 | 90 | 110 | 125 | 90 | 110 | 125 |
| Wet | kV | 40 | 50 | 55 | 75 | 100 | 60 | 90 | 100 |
| Withstand volt.impulse | kV | 90 | 110 | 150 | 170 | 200 | 140 | 180 | 200 |
| RIV Data | Test volt. TO ground | kV | 15 | 15 | 22 | 30 | 44 | 22 | 30 | 44 |
| Max RIV at 1000 KHz | uV | 8000 | 8000 | 12000 | 16000 | 25000 | 12000 | 16000 | 25000 |
| Power Frequency Puncture Voltage | kV | 150 | 150 | 200 | 210 | 250 | 150 | 200 | 210 |
| Approx.Weight | kg | 1.8 | 2 | 5 | 11 | 14 | 4.7 | 9.1 | 12.5 |