High Voltage 160kn Disc Suspension Toughened Glass Insulator U160B

Model
Nature of the Manufacturer
Manufacturer
Product Category
Glass Insulators
Place of Origin
City, Province
Overview
Glass insulator has superior mechanical properties, good anti flashover performance, excellent corrosion resistance, good aging resistance, good structural stability, high efficiency and light weight.
Product Details

Product Design Drawings

High Voltage 160kn Disc Suspension Toughened Glass Insulator U160B (4)

Product Description

IEC designationU160B/146U160B/155U160B/170
Diameter Dmm280280280
Height Hmm146155170
Creepage distance Lmm400400400
Socket couplingmm202020
Mechanical failing loadkn160160160
Mechanical routine testkn808080
Wet power frequency withstand voltagekv454545
Dry lightning impulse withstand voltagekv110110110
Impulse puncture voltageP.U2.82.82.8
Power frequency puncture voltagekv130130130
Radio influence voltageμv505050
Corona visual testkv18/2218/2218/22
Power frequency electric arc voltageka0.12s/20Ka0.12s/20Ka0.12s/20Ka
Net weight per unitkg6.76.66.7

Product Definition

Glass insulators an insulator made of tempered glass. Its surface is in the state of compression prestress, such as crack and electrical breakdown, glass insulator will break into small pieces, commonly known as "self-explosion". This feature eliminates the need for "zero value" detection of glass insulators during operation.
The glass insulator is the crystallization of the combination of glass and insulator. Because of the characteristics of glass compared with electric porcelain, glass insulators have better stability in electrical and mechanical characteristics, and their transparency makes it easy to check the damage during operation, so that the regular electrified preventive test for insulators is cancelled. The electrical strength of glass generally remains the same throughout its operation, and its aging process is much slower than that of porcelain. Therefore, glass insulators are mainly abandoned due to self-damage, which occurs within the first year of operation, whereas the defects of porcelain insulators begin to be discovered only after several years of operation.

xcp

This standard specifies the general technical requirements, selection principles, inspection rules, acceptance, packaging and transportation, installation and operational maintenance, and operational performance testing for ac overhead line insulators with nominal voltages above 1000V.

This standard is applicable to disk-type suspended porcelain and glass insulators (insulators for short) used in ac overhead power lines, power plants and substations with nominal voltage above 1000Y and frequency 50Hz. The altitude of the installation site must be lower than 1000m, and the ambient temperature must range from -40 ° c to +40 ° c. 2 Normative reference files

Product scenario application

ffff