FN12 indoor air pressure LBS. It is a three phase H.V. switch equipment of 12kV, 50Hz for breaking or closing load current., no-load transformer cable charging current and closing short-circuit current.
General:
It is a three phase H.V. switch equipment of 12kV, 50Hz for breaking or closing load current., no-load transformer cable charging current and closing short-circuit current. The load switch with earth switch can bear short-circuit current.
It is made up of FN12-12D load switch and S()LAJ-12(XRNT()-10) H.V. current-limiting fuse box. It can break any current, load switch breaking working current and fuse box breaking short-circuit current, jointly breaking any current between short-circuit current. Meantime, fuse box make the switch off of with the striker.
Service Condition:
A. The ambient air temperature: Max.: +40 °C. Min: -10 °C.
B. The altitude ≤ 1000m.
C. The relatire humidity of air. daily average ≤ 90%. monthly average ≤ 95%.
D. The ambient air should not be obviously polluted by corrosivity or the flammability gas and geam. etc.
E. Without frequent shake.
F. Enviroment degree: grade Ⅱ.
If requirements are not mentioned above, users can fix them with the manufacturer.
Technical data:
| Number | Name | Unit | FN12-12D/630-20 | FN12-12D.R/100-31.5 |
| 1 | Rated voltage | kV | 12 |
| 2 | Rated frequency | Hz | 50 |
| 3 | Reated current | A | 630 | 100 |
| 4 | Lighting impulse resisting voltage | kV | 75/85 |
| 5 | 1min power frequency with stand voltage | kV | 42/48 |
| 6 | Rated heat - stability current | kA | 20(4S) |
| 7 | Rated machine-stability current | kA | 50 |
| 8 | Rated closing current (peak) | kA | 50 | |
| 9 | Rated short-circuit breaking current | kA | | 31.5 |
| 10 | Rated transfer current | kA | | 1.5 |
| 11 | Max. breaking current | kA | 1.8 |
| 12 | Breaking no-load transformer capacity | Kva | 1250 |
| 13 | Rated cable charging current | A | 10 |
| 14 | Rated power load current breaking times | time | >100 |
| 15 | Switch-off time of rated power load current switch on-and-off | S | | >0.06 |
| 16 | Earth switch heat-stability current | kA | 20(2S) | 20(2S) |
| 17 | Earth switch heat-stability curreak (peak) | kA | 50 | 50 |
| 18 | Motor operating power valtage | V | AC220,DC48 |