High Voltage SF6 Gas Circuit Breaker

Model
Nature of the Manufacturer
Other
Product Category
Switchgear Components
Place of Origin
City, Province
Overview
HR4 type high voltage indoor SF6 gas circuit breaker with two installation way by drawable/Fixed. which is widely application for three-phase AC power system of rated voltage from 3.3kV up to 36kV at frequency 50/60Hz.
Product Details

High voltage sf6 gas circuit breaker

General

HR4 type high voltage indoor SF6 gas circuit breaker with two installation way by drawable/Fixed. which is widely application for three-phase AC power system of rated voltage from 3.3kV up to 36kV at frequency 50/60Hz, especially using for power plant, transformer substation, petrol chemical industry, metallurgy, manufacturing industry, airport, residential area, etc.

Its high performance switchgear which will reduce over-voltage and harmonic impulse at max for by a normal or fault breaking or making.

Its easy for interchange for VD4,SF1,HD4 type switchgear like type KYN28 or AMS, ABB type ZS1 series, etc.

This circuit breaker is follow per standards like:

IEC62271-100AC high voltage circuit breaker,

GB1984-2003 AC high voltage circuit breaker

JB3855 3.6-40.5Kv indoor AC High voltage circuit breaker

DL/T403 Specification of 12-40.5kV indoor High voltage vacuum circuit breaker.

 

Offering

Autopuffer breaking technique
Electric arc extinction without chopped current
No restriking after breaking
Rapid recovery of the dielectric properties of the means of extinction
Withstand insulation voltage even at zero relative pressure (*)
Breaking up to 30% of the rated breaking capacity even at zero relative pressure (*)
Sealed-for-life poles
Test for checking gas tightness carried out three times on each piece of apparatus

 

Compact dimensions
Fixed and withdrawable version

Stored energy operating mechanism with anti-pumping device as standard common to the whole circuit-breaker series

Mechanical safety

locks against incorrect operations Simple personalisation thanks to a com- plete range of accessories

Maintenance-free
SF6 gas pressure control device (on request).

Fields of application
HM4 circuit-breakers are used in power distribution to control and protect lines, transformer and distribution substations, motors, transformers, capacitor banks, etc.
Thanks to the SF6 autopuffer breaking technique, the HM4 circuit-breakers do not generate operating overvoltages, and are therefore also highly suitable for retrofitting, upgrading and enlarging older installations where the motor, cable, etc. insulating materials may be particularly sensitive to dielectric stresses.

 

Breaking technique
The breaking technique of HD4 circuit-breakers is based on compression and self-blast techniques to obtain top performances at all service current values, with minimum arc times, gradual arc extinction without chopping, and no restriking or operating overvoltages.
The HM4 series brings to medium voltage the advantages of the “autopuffer" breaking technique already used in high voltage.

 

Standards and approvals
HM4 circuit-breakers comply with IEC 62271-100, CEI 17-1 file 1375 Standards and with those of major industrialised countries.
They have undergone the following tests and guarantee safety and reliability of the apparatus in service in all   installations.
Type tests: heating, withstand insulation at industrial and impulse frequency, short-time and peak withstand current, mechanical duration, making and breaking of short-circuit currents;
Individual tests: insulation with voltage at industrial frequency in the main circuits and insulation of the auxiliary and control circuits, measurement of the main circuit resistance, mechanical and electrical operation.
The HM4 circuit-breakers are tested according to the requirements of the IEC 62271-100 Standard (class E2 - table 21) and guarantee suitability for use in overhead lines, with rapid reclosing cycle.

Service safety
Thanks to the availability of a complete range of mechanical and electrical locks (on request), safe distribution switchgear can be constructed using HM4 circuit-breakers. The locking devices have been designed to prevent incorrect operations and to carry out inspection of the installation, ensuring maxi- mum operator safety.

Technical Service:

ROCKWILL®, China. Provide with best support

Tel: 0086-

barry@rockwill.cn

a) Air temperature: Maximum temperature: +40°C; Minimum temperature:-25°C

b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .

c) Altitude above sea level: Maximum installation altitude: 2500m

d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

e) No frequent violent shake

SF6 circuit-breaker
 
HM4-12
HM4-17
HM4-24
HM4-36
HM4-40
Standards
 
IEC 62271-100 CEI 17-1 (file  1375)
Rated voltage
Ur [kV]
12
17.5
24
36
40.5
Rated insulation voltage
Us [kV]
12
17.5
24
36
40.5
Withstand voltage at 50 Hz(1min)
Ud [kV]
28
38
50
70
95
Impulse withstand voltage
Up [kV]
75
95
125
170
185
Rated frequency
Fr [Hz]
50/60
Rated normal current (40 °C)
Ir [A]
630/800/1250/1600/2000/2500/3150/3600
Rated breaking capacity
Isc [kA]
12.5/16/25/31.5/40/50
Rated short-time
Ik [kA]
12.5/16/25/31.5/40/50
Making capacity
Ip [kA]
31.5/40/50/63/80/100/125
Operation sequence
 
O-0.3s-CO-15s-CO
Opening time
[ms]
45
45
45
45
45
Arcing time
[ms]
10~15
10~15
10~15
10~15
10~15
Total breaking time
[ms]
55~60
55~60
55~60
55~60
55~60
Closing time
[ms]
80
80
80
80
80
Maximum overall dimensions
H [mm]
640
649
818
730/1060
790/1123
W[mm]
493
618
730
880/955
748/805
D [mm]
496
496
620
695
833
Pole centre distance
I [mm]
150
210
275
350
275
Weight
[kg]
114
114
119
128
190
Absolute SF6 gas pressure
[kPa]
380
380
380
380
450
Operating temperature
[°C]
-5~+40
Tropicalization
 
IEC:  60068-2-30, 60721-2-1
Electromagnetic compatibility
 
IEC: 60694

indoor sf6 gas circuit breaker dimension

gas insulated circuit breaker drawing

rockwill gas insulated circuit breaker dimension