Prefabricated compact substation, also known as compact substation or package substation. It is consists of high-voltage switchgear, distribution transformer and low-voltage power distribution device
Prefabricated substation, also known as compact substation or package substation. It is consists of high-voltage switchgear, distribution transformer and low-voltage power distribution device, which are prefabricated indoor and outdoor compact power distribution equipment in a factory according to a certain wiring scheme. At the same time, it is installed in a moisture-proof, rust-proof, dust-proof, rodent-proof, fire-proof, anti-theft, heat- insulating, fully enclosed, movable steel structure box, especially suitable for urban network construction and transformation. A brand new substation. Box-type substations are suitable for mines, factories, oil and gas fields and wind power stations.
Features:
1. Substation exterior wall
Place the steel bar in the mold, add glass fiber reinforced concrete (Composite ciment verre or CCV), after solidification, use Outdoor anti-rust paint for painting.
2. Substation Base
Using rigid strength channel steel and reinforced steel, through multiple anti-rust and painting processes, it is safe, firm and corrosion-resistant.
3. Metal Door Frame
Optional1: The door frame made of high-strength steel and the outer door of the substation made of glassfiber cement blocks not only ensure the strength, but also ensure the durability andcorrosion resistance.
Optional2: The door frame made of high-strength steel and the outer door of the substation made of Composite metal plate, reduce weight and increase heat dissipation.
4. Ventilation
Shutters type vent is good for Waterproof, dustproof, heat dissipation.
5. Installation Method
Install directly on the concrete foundation
Environment Conditions
1. Air temperature: Maximum temperature: +40℃; Minimum temperature:-25℃
2. Humidity: Monthly average humidity 95%; Daily average humidity 90% .
3. Altitude above sea level: Maximum installation altitude: 2500m
4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 5e) No frequent violent shake
Characteristics of Enclosure
Characteristics | Value |
Dimension | According to the transformer capacity 4000*2500*2100,5000*2500*2100mm Wdith*Height*Depth |
Equipment weight | 4600kg, 5100kg,5500kg |
Protection degree | IP4X |
Mechanical impact resistance | IK10 |
Enclosure finish | Anti-rust, paint treatment |
Number of compartment | 3 |
Number of doors | 6 (can also be designed as per customer's requiement) |
Characteristics of 24kV RMU
Characteristic | value |
Insulation level | 24kV |
Service voltage | 15kV |
Power frequency withstand voltage | 50kV |
Lightning impulse withstand voltage | 125kV |
Allow short-time current | 20kA |
Short-term current peaks | 50kA |
Busbar rating | 630A |
Characteristics of H61 Transformer
Characteristic | Value |
Primary Voltage | 15kV |
Secondary voltage | 0.4kV |
Capacity | 250kVA/400kVA/630kVA |
Winding material | Copper |
Vector group | Dyn11 |
Tap changer | ±2*2.5% |
Impedance | 4% |
Ambient temperature | -20℃ to 40 ℃ |
temperature rise | 65℃ |
No load losses | 650W/930W/1300W |
Load losses | 4200W/6000W/8400W |
Characteristics of LV Switchgear
The body of GGD AC LV fixed type switchgear adopts universal cabinet type.
Framework is assembled with 8MF cold bending bar steel through part welding. Framework components and special mating elements are matched by bar steel.
pointed factory for ensuring the precision and quality of cabinet. Components of universal cabinet is designed according to module principle, and with 20 modulus mounting hole and high universal coefficient.