Container type unitized compact substation from Rockwill Electric. It complies with IEC standard, and it is easy for transpotation and installation, high quality and strong enough for loading and lifting.
Container type unitized compact substation
Container type unitized CSS compact substation is a complete type tested per latest IEC standard 62271-202 which is comprising a outdoor enclosure containing medium voltage (MV) switchgear, power or distribution transformers, low voltage (LV) switchboards, busbar or cable connections and auxiliary equipment to feeder elctric power by a step down power & distribution transformer from medium voltage systems.
The container type CSS compact substation is easy for transpotation and installation, high quality and strong enough for loading and lifting.
What other type substation does Rockwill make??
>>> Mining substation <<<
>>> Unitized skid substation <<<
>>> Package substation <<<
>>> substation <<<
>>> Padmount transformer substation / ANSI standard US substation <<<
>>> Mini substation / Miniature substation <<<
>>> kiosk substation <<<
>>> Portable substation <<<


------------------------------------------------
Why choose Rockwill?
>>> More than 20 years experience <<<
>>> Rich experience on oversea market <<<>>> Quality with competitive price and best service <<<、
------------------------------------------------
Technical Service:
ROCKWILL®, China. Provide with best support
Tel: 0086-
: barry@rockwill.cn
operation Condition:
Operation temperature:-25℃~40℃
Humidity:≤95%/day,≤90%/month
Average temperature:≤30%month,20%/year
Wind velocity:≤30%/sec
duty level :3
Earthquake :Horizontal≤30%m/s2,Vertical≤30%m/s2
Gradient:≤3℃
Protection degree:IP30
Characteristic &Structure Features:
·Two types of box-type transformer substation,corridor type and non-corridor type,welded frame by excellent
·Anticorrosive steel,hot-galvanizing steel base;
·box-type transformer substation has 3 parts,HVcabinet,transformer cabinet.layout maybe customized.
·two-layer roof with air inside to prevent temperature rising effectively
·natural air cooling,optional forced air cooling,optional automatic anti-congeal equipment
·different type od load switch and fuse combination to protect the transformer
·terminal power supply,ring supply and double power supply.
·welded body of LV cabinet,screen type nameplate.
Circuit Schemtic Diagram

General
YB() series products is a kind of set of equipment which assembles the MV switch apparatus, transformer, LV distribution equipment together according to fixed connection scheme. This series substation is suitable for neighborhood unit, hotel, large-scale work site and high building that the voltage is 12kV /24kV/36kV/40.5kV, the frequency is 50Hz and the capacity is under 2500kvA.

Service environment
a) Air temperature: Maximum temperature: +40℃; Minimum temperature:-25℃
b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level: Maximum installation altitude: 2500m
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake
Main technical specifications
Name | Unit | HV equipment | Transformer | LV Equipment |
Rated voltage | kV | 12/24/36 | (12/24/36)/0.4 | 0.4 |
Rated current | A | 630 | 3/75-150/3750 | Less than 4000 |
Frequency | Hz | 50 |
Rated Capacity | kVA | 50-2500 |
Pfr withstand | kV | 42/50/70/95 | 2.5 |
BIL | kV | 75/125/170/185 | |
Crust Protection Grade | | IP23 | Oil type 55; dry type 65 | IP23 |
Noisy Grade | dB | | | |
Appearance Dimensions | mm | According to primacy wiring circuit schema |
 |  |  |
HV Room | LV Room | Transformer Room |
Main Designation Characteristics
The crust of the substation is designed according to the foreign advanced technology and physical reality. We provide many kinds of crust material such as aluminum alloy steel composite stainless steel board and non metal material(glass fiber).
The HV side use charge switch or vacuum circuit breaker. The transformer could be oil type hermetically-sealed type and dry type.
The proof of the box is double layers structure and between the layers is filled with foam. There are independent boards in HV and LV room, and in the transformer room will install auto thermal controller heater and cooling equipment.
Note: we offer special customized products according to client’s requirement.

36kV/40.5kV Prefabricated Substation Characteristics
This type substations are the HV side 40.5 kV, LV side 0.4-12 kV and 3 phase outdoor completeequipment .It is wide used in cities , towns ,factories and oil fields, wharfs etc. It is also used insome construction sites. The characteristics are small volume, convenient installation, low cost,high automation safe and reliable operation. Substation is combined with HV switch room,LVswitch room, relay room and transformer room.
Main technical specifications for 36kV/40.5kV Prefabricated Substation
Name | Unit | HV equipment | Transformer | LV Equipment |
Rated voltage | kV | 40.5 | 40.5/12/0.69/0.4 | 12/6.3/0.69/0.4 |
Rated current | A | Less than 1250 | | Less than 4000 |
Frequency | Hz | 50 |
Rated Capacity | kVA | 1250-20000 |
Pfr withstand | kV | 70/95 | 42/2.5(Auxiliary) |
BIL | kV | 170/185 | 75 |
Crust Protection Grade | | IP23 | Oil type 55; dry type 65 | IP23 |
Noisy Grade | dB | | | |
Appearance Dimensions | mm | According to primacy wiring circuit schema |
|
|
36kV/40.5kV prefabricated transformer substation |
Main Primacy Wiring Circuit Schemas for Substation(40.5kV)




Note: we offer special customized products according to client’s requirement.
This equipments also belong to this Prefabricated substation category with a compact and special function of HV, LV and Transformer are all underground. People can enter into it through a well.
This substation is suitable for installing in square seeded strip and park The clients can choose half-buried type or whole-buried type.

Sketch map of half-buried substation

Sketch diagram of whole-buried substation

Miniaturization Intelligent Prefabricated Substation
This series pre-fabricated substation uses imported SF6 ring switch as its HV incoming and outgoing network realized the power ring system easily. And the substation selects integrated automation system which can realize unattended mode.