Welcome Customer !

Membership

Rockwill Electric Group
Free Member ·1YRS
Other

Main Products: 开关设备

Xwboo>Products

Rockwill Electric GroupFree·1YRS

  • E-mail

    barry@rockwill.cn

  • Phone

    +86-577-27869969

  • Address

    Wengyang Industrial Zone,Wenzhou City, Zhejiang Province,China.

Contact Now

6kV to 15kV Oil Immersed Distribution Transformer

Model
Nature of the Manufacturer
Other
Product Category
Transformer Equipments
Place of Origin
City, Province
Overview
China three phase oil immersed distribution transformer. Rated voltage: 6kV,6.3kV,10kV,10.5kV,11kV,13.2kV,13.8kV,15kV. Capacity: 10kVA, 30kVA, 50kVA, 63kVA, 80kVA, 100kVA, 125kVA, 160kVA, 200kVA, 250kVA, 315kVA, 400kVA, 500kVA, 630kVA, 800kVA, 1000kVA, 1250kVA, 1600kVA.
Product Details

6kV 6.3kV 10kV 10.5kV 11kV 13.2kV 13.8kV 15kV Oil Immersed Distribution Transformer

China 6kV - 15kV three phase oil immersed distribution transformer which is most used in power plant, power grid transmission and distribution station. It is manufactured by Rockwill Electric Group which has dedicated in power industry for 30 years. The distribution transformer has high quality and good price for winning our clients' trusts. 

 

Features of 6kV to 15kV Oil Immersed Distribution Transformer:

1. Rated voltage: 6kV,6.3kV,10kV,10.5kV,11kV,13.2kV,13.8kV,15kV

2. Rated power capacity: 10kVA, 30kVA, 50kVA, 63kVA, 80kVA, 100kVA, 125kVA, 160kVA, 200kVA, 250kVA, 315kVA, 400kVA, 500kVA, 630kVA, 800kVA, 1000kVA, 1250kVA, 1600kVA

3, Two windings or three windings

4, On-load or no-load voltage tapping changer

5. Frequency: 50Hz /60Hz

6. Vector group: Dyn11, Yyn0, Ynd11, or others

7. Cooling: ONAN/ ONAF/ OFAF

8. Tap changer:3 levels; 5 levels; 7 levels; 13 levels; 17 levels

 

Service Condition of 6kV to 15kV Oil Immersed Distribution Transformer

1. Suitable for indoor or outdoor application

2. Air temperature: Maximum temperature: +40℃; Minimum temperature:-30℃

 a. Humidity: Monthly average humidity 95%; Daily average humidity 90% .

 b. Altitude above sea level: Maximum installation altitude: 2000m.

3. Max wind speed:35M/s

 a. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

 b. No frequent violent shake

kVA

Voltage

VECTOR GROUP

LOSSES

No-load Current

Weight(kg)

 

Overall dimension mm

 

H.V. kV

L.V V

No-load loss

Load loss

 

Oil weight

Total weight

L

W

H

20

6
6.3
10
10.5
11
13.2

380
400
415
433

Yyn0
Dyn11
Yzn11

90

530

2.3

55

230

720

440

855

30

100

600

2.1

75

305

750

500

990

50

130

870

2.0

80

405

800

480

1030

63

150

1040

1.9

95

455

830

615

1060

80

180

1250

1.9

105

510

840

580

1115

100

200

1500

1.8

120

530

890

645

1145

125

240

1800

1.7

130

670

910

600

1185

160

280

2200

1.6

140

810

910

700

1280

200

340

2600

1.5

160

890

1000

760

1240

250

400

3050

1.4

175

1020

1285

730

1290

315

480

3650

1.4

185

1170

1280

740

1385

400

570

4300

1.3

215

1410

1310

750

1432

500

680

5100

1.2

260

1645

1365

765

1510

630

810

6200

1.1

310

2070

1485

815

1615

800

980

7500

1.0

370

2445

1640

930

1590

1000

1150

10300

1.0

425

2800

1860

1120

1630

1250

1360

12000

0.9

480

3320

1860

1120

1830

1600

1640

14500

0.8

550

4175

1975

1175

1900

Similar Product Recommend