36kV Air Insulated Switchgear

Model
Nature of the Manufacturer
Other
Product Category
Metal Switchgear and RMU
Place of Origin
City, Province
Overview
iSafeRing is a SF6 insulated ring main unit for the secondary distribution network. iSafeRing can be supplied in 10 different configurations suitable for most switching applications in 36 kV dis
Product Details
36kv Air Insulated Switchgear
 
Air insulated SF6 Ring Main Unit
 
General

HXGN15 series unit type SF6 ring net cabinet with SF6 load switch as main switch, for whole cabinet is suitable for electric distribution automation and compact also expandable metal close switchgear. It characters in its simple structure, flexible operation, reliable interlocking and convenient installation etc., which can provide the satisfactory technical projects both for different application occasions and users. With the adoption of sensor technology and the protection relay up to date, plus the advanced technology and flexible assembly project, HXGN15 unit type SF6 ring net cabinet can completely meet the requirement of continuously variable market. It can take self-produced FLBS36 SF6 load break switch ; also according to user’s demand can be assembled with the internationally top-ranking VB4 series vacuum circuit breaker with permanent magnetic mechanism made by AREVA or HD4 type SF6 circuit breaker made by AREVA or HD4 type SF6 circuit breaker made by ABB or with our VS1-12 type vacuum circuit breaker with permanent magnetic mechanism. Operational methods for the main switch inside ring main unit can be either manual or electric power driven.
 
 
Environmental Conditions

(1) Suitable Altitude: ≤2000mSuitable
(2) Temperature: -40℃ ~ +55℃Relative
(3) Humidity: Daily mean ≤95%, monthly mean ≤90%
(4) Gradation of Earthquake Damage: ≤ Leve
 
 
Air insulated SF6 Ring Main Unit Main technical specifications
No
Item
Unit
Parameter
1
Rated voltage
kV
36
2
Rated frequency
Hz
50/60
3
Rated current
A
630(1250*)
4
1min Power frequencywithstand voltage
wet
kV
70
dry
kV
85
5
Lightning impulse withstand voltage
kV
170
6
Rated short circuit breaking current (peak)
kA
63
7
Rated active load and close circuit breaking current
A
50
8
Rated transferring current
A
1200
9
Rated short circuit making current (peak)
kA
63
10
Rated cable(line) charging breaking current
A
50 and 1050/10
11
Cable charge breaking current in earthing fault
A
20
12
Rated withstand current (peak)
kA
63
13
Short time withstand current (2s)
kA
20
14
Mechanism life
times
2000