The enclosure is made of aluminium-zinc plated steel sheet by CNC machine, high precise dimension, short production cycle, excellent mechanical strength and nice appearance. The busbar compartment, VC
17.5kV Air Insulated Metal Clad Withdrawable Switchgear
General
KYN28 indoor metal-clad withdrawable switchgear hereinafter short as switchgear) is a complete power distribution device for3.6-24kv.3-phase AC 50Hz single-bus and single-bus sectionalized system. It is mainly used for power transmission ofmiddle/small generators in power plants: power receiving, transmission for substations in power distribution and power system offactories, mines and enterprises, and starting of large high-voltage motor, etc..so as to control, protect and monitor the system.The switchgear meets IEC298.GB3906-91In addition to be used with domestic VS1 vacuum circuit breaker, it can also be usedwith 3AH5 from Siemens domestic ZN65A.and VB2 from GE, ete it is truly a power distribution device with good performanceIn order to meet the requirement for wall mounting and front-end maintenance, the switchgear is equipped with a special currenttransformer, so that the operator can maintain and inspect it in front of the cubicle.KYN61-40.5( same as unigear Z3.2) air-insulated meta-clad withdrawable switchgear( hereinafter as "switchgear") is a kind ofMV switchgear. It is designed as withdrawable module type panel, and the withdrawable part is fitted with VD4-3 6E, VD4-40.5withdrawable vacuum circuit breaker manufactured by Cooper Nature company. It can also be fied with isolation truck, PTtruck, fuses truck and so on It is aplicable to three phase AC 50/60 Hz power svstem. and mainly used for the transmision anddistribution of electrical power and control, protection, monitoring of the circuit.
Standards and specifications
IEC60694 The common technical requirements ofhigh voltage switchgear and controlgear
IEC62271-200 A.C.metal enclosed switchgear and controlgear at the rated voltage of 1kV~52k VE
CB62271-100 High voltage switchgear and controlgear-Part 100:Hi gh voltage A.C. circuit breaker
GB3906 3.6~ 40.5kV alternating current metal enclosed switchgea r and controlgear
GB1984 High voltage alternating current circuit breaker
GB/T11022 The common technical requirements of high voltage switchgear and controlgear
12kV & 24kV KYN28 Metal Clad Air Insulated Switchgear |
No | Item | Unit | Parmeter |
1 | Rated voltage | kV | 7.2kV,12kV,17.5kV,24kV |
2 | Ratec frequency | Hz | 50/60 |
3 | Rated current | A | 630,1250,1600,2000,2500,3150,4000 |
4 | Branch busbar rated current | A | 630,1250,1600,2000,2500,3150,4000 |
5 | Main busbar rated current | A | 630,1250,1600,2000,2500,3150,4000 |
6 | 1 min power frequency withstand voltage(wet dry) | kV | 38/48,50/60/60/65 |
7 | Lightning impulse withstand voltage | kV | 75,95/125 |
8 | Rated short circuit breaking current(peak) | kA | 40/50/63/80/100 |
9 | Short time withstand current(4s) | kA | 20/25/31.5/40 |
10 | Protection type | | IP4X for housing |
Vaccum Circuit Breaker
Description | Unit | Value |
Rated voltage | kV | 17.5 |
Rated short-time power frequency withstand voltage (1min)(1min) | 50 |
Rated lightning impulse withstand voltage (peak) | 125 |
Rated freq | Hz | 50,60 |
Rated current | A | 630 | 630 | 1250 | 1600 | 1250 | 1600 | 1600 | 2000 |
1250 | 1250 | 2000 | 2500 | 2000 | 2500 | 2500 | 3150 |
| | 3150 | | 3150 | 4000* | 4000* |
Rated short-circuit drop-out current | kA | 20 | 25 | 31.5 | 40 | 50 |
Rated short time withstand current | 20 | 25 | 31.5 | 40 | 50 |
Rated short time continual time | s | 4 |
Rated peak withstand current | kA | 50 | 63 | 80 | 100 | 125 |
Rated short-circuit closing current | 50 | 63 | 80 | 100 | 125 |
Rated single/ back-to-back capacitor bank drop-out current | A | 630/400(40kA is 800/400) |
Rated capacitor bank closing inrush current | kA | 12.5(frequency no more than 1000Hz) |
Opening time (rated volt.) | ms | 20~50 |
Closing time (rated volt.) | 35~70 |
Mechanical life | Times | 30,000 |
Rated break times for rated short drop out current | 50 |
Rated operation voltage | V | AC110/220 DC110/220 |
Rated current of power storing motor | W | 70 |
Average opening speed | m/s | 0.9~1.3 |
Average closing speed | 0.4~0.8 |
Rated operation procedure | | opening-0.3s-closing opening-180s-closing opening |