The enclosure is made of aluminium-zinc plated steel sheet by CNC machine, high precise dimension, short production cycle, excellent mechanical strength and nice appearance. The busbar compartment, VC
10kV Air Insulated Metal Clad Switchgear
Standards
The switchgear and main apparatus contained in it comply with the latest IEC Standards:
• IEC 62271-1 for general purposes
• IEC 62271-200 for the switchgear
• IEC 62271-102 for the earthing switch
• IEC 62271-100 for the circuit-breakers
• IEC 60071-2 for the insulation coordination
• IEC 62271-106 for the contactors
• IEC 60265-1 for the switch-disconnectors
• IEC 60529 for degree of protections0
Service environment:
a) Air temperature:Maximum temperature: +40℃; Minimum temperature:-25℃
b) Humidity:Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level:Maximum installation altitude: 2500m
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake
Vaccum Circuit Breaker
Description | Unit | Value |
Rated voltage | kV | 10 |
Rated short-time power frequency withstand voltage (1min)(1min) | 42 |
Rated lightning impulse withstand voltage (peak) | 75 |
Rated freq | Hz | 50,60 |
Rated current | A | 630 | 630 | 1250 | 1600 | 1250 | 1600 | 1600 | 2000 |
1250 | 1250 | 2000 | 2500 | 2000 | 2500 | 2500 | 3150 |
| | 3150 | | 3150 | 4000* | 4000* |
Rated short-circuit drop-out current | kA | 20 | 25 | 31.5 | 40 | 50 |
Rated short time withstand current | 20 | 25 | 31.5 | 40 | 50 |
Rated short time continual time | s | 4 |
Rated peak withstand current | kA | 50 | 63 | 80 | 100 | 125 |
Rated short-circuit closing current | 50 | 63 | 80 | 100 | 125 |
Rated single/ back-to-back capacitor bank drop-out current | A | 630/400(40kA is 800/400) |
Rated capacitor bank closing inrush current | kA | 12.5(frequency no more than 1000Hz) |
Opening time (rated volt.) | ms | 20~50 |
Closing time (rated volt.) | 35~70 |
Mechanical life | Times | 30,000 |
Rated break times for rated short drop out current | 50 |
Rated operation voltage | V | AC110/220 DC110/220 |
Rated current of power storing motor | W | 70 |
Average opening speed | m/s | 0.9~1.3 |
Average closing speed | 0.4~0.8 |
Rated operation procedure | | opening-0.3s-closing opening-180s-closing opening |
The enclosure is made of aluminium-zinc plated steel sheet by CNC machine, high precise dimension, short production cycle, excellent mechanical strength and nice appearance. The busbar compartment, VCB handc art compartment, cable compartment and relay compartment are separated by metal sheet. Flexible operation for handcart movement, clear position instruction, the earthing switch allow to making short circuit current and creditable mechanical interlock.
Technical data
Rated voltage | kV | 10 |
Rated insulation voltage | kV | 12 |
Rated power frequency withstand voltage | kV 1min | 28 |
Rated lightning impulse withstand voltage | kV | 75 |
Rated frequency | Hz | 50/60 |
Rated short time withstand current | kA 3 s | up to 50 |
Peak current | kA | up to 125 |
Internal arc withstand current | kA 1s | up to 50 |
Main busbar rated current | A | up to 4000 |
Circuit-breaker rated current | A | 630 1250 1600 2000 2500 3150 |
Circuit-breaker rated current with forced ventilation | A | 3600 4000 |