| Input |
Available Inverters / PCS | SUN2000-200KTL / SUN2000-215KTL / SUN2000-185KTL / LUNA2000-200KTL |
Maximum LV AC Inputs | 34 |
AC Power | 6,800 kVA @40℃ 1 |
Rated Input Voltage | 800 V |
LV Main Switches | ACB (2,900 A / 800 V / 3P, 2 x 1 pcs), MCCB (250 A / 800 V / 3P, 2 x 17 pcs) |
| Output |
Rated Output Voltage | 11 kV, 15 kV, 20 kV, 22 kV, 30 kV, 33 kV, 35 kV 2 | 13.8 kV, 34.5 kV 2 |
Frequency | 50 Hz | 60 Hz |
Transformer Type | Oil-immersed, Conservator Type |
Transformer Cooling Type | ONAN |
Transformer Tappings | ± 2 x 2.5% |
Transformer Oil Type | Mineral Oil (PCB Free) |
Transformer Vector Group | Dy11-y11 |
Transformer Min. Peak Efficiency Index | Tier 1 or Tier 2 In Accordance with EN 50588-1 |
RMU Type | SF6 Gas Insulated |
RMU Transformer Protection Unit | MV Vacuum Circuit Breaker Unit |
RMU Cable Incoming / Outgoing Unit | Direct Cable Unit or Cable Load Break Switch Unit |
Auxiliary Transformer | Dry Type Transformer, 5 kVA, Dyn11 |
Output Voltage of Auxiliary Transformer | 400 / 230 Vac or 220 / 127 Vac |
| Protection |
Transformer Monitoring & Protection | Oil Level, Oil Temperature, Oil Pressure and Buchholz |
Protection Degree of MV & LV Room | IP 54 |
Internal Arcing Fault Classification of YBS | IAC A 20 kA 1s |
MV Relay Protection | 50/51, 50N/51N |
LV Overvoltage Protection | Type I+II |
Anti-rodent Protection | C5 Medium in accordance with ISO 12944 |
| Features |
2 kVA UPS | Optional 3 |
MV Surge Arrester for MV VCB | Optional 3 |
| General |
Dimensions (W x H x D) | 6,058 x 2,896 x 2,438 mm (20’ HC Container) |
Weight | < 22 t |
Operating Temperature Range | -25℃ ~ 60℃ 4 (-13°F ~ 140°F) |
Relative Humidity | 0% ~ 95% |
Max. Operating Altitude | 1,000 m 5 | 1,500 m 5 |
MV-LV AC Connections | Prewired and Pretested, No Internal Cabling Onsite |
LV & MV Room Cooling | Smart Cooling without Air-across for Higher Availability |
Communication | Modbus-RTU, Preconfigured with Smartlogger3000B |
Applicable Standards | IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1 |