ApplicationTSC-D series AC Contactor is suitable for using in the circuits up to the rated voltage660V AC 50Hz or 60Hz, rated current up to 95A, for making, breaking, frequently start-ing & controlling the AC motor. Combined with the auxiliary contact block, delay timer & machine-interlocking device etc, it becomes the delay contactor, mechanical inter-locking contactor, star-delta starter. With the thermal relay, it is combined into the elec-tromagnetic starter. The products comply with IEC60947-4.Specification
| Model | TSC-D40 | TSC-D50 | TSC-D65 | TSC-D80 | TSC-D95 |
| Rated working current(A) | AC3 | 40 | 50 | 65 | 80 | 95 |
| AC4 | 16 | 20 | 25 | 32 | 38 |
| AC3 capacity of phase 3squrrel-cage motor AC3(KW) | 220/230V | 11 | 15 | 18.5 | 22 | 25 |
| 380/400V | 18.5 | 22 | 30 | 37 | 45 |
| 415V | 22 | 25 | 37 | 45 | 45 |
| 500V | 22 | 30 | 37 | 55 | 55 |
| 660/690V | 30 | 33 | 37 | 45 | 55 |
| Rated heat current (A) | 60 | 80 | 80 | 95 | 110 |
| Electrical life | AC3x 100000 | 80 | 60 | 60 | 60 | 60 |
| AC4x100000 | 15 | 15 | 15 | 10 | 10 |
| Mechanical life x 10 | 800 | 800 | 800 | 600 | 600 |
| Number of the contacts | 3P+NO+NC |