Welcome Customer !

Membership

Haivo Electrical Co.,Ltd
Free Member ·1YRS
WenZhou,ZheJiang
Manufacturer

Main Products: Surge Protective Device|Surge Protector

Xwboo>Products

15kv Porcelain Pin Insulator for Station Post(BS)

Model
Nature of the Manufacturer
Manufacturer
Product Category
Porcelain Insulator
Place of Origin
City, Province
Overview
Porcelain insulators,also named ceramic Insulators are made from clay, quartz or alumina and feldspar, and are covered with a smooth glaze to shed water. Insulators made from porcelain rich in alumina are used where high mechanical strength is a criterion. Porcelain has a dielectric strength of about 4–10 kV/mm.It also has perfect dielectric performance.Porcelain insulators are widely used in overhead transmission lines to provide mechanical support and electrical protection, as well as in distribution lines and su......
Product Details

Insulators are a special insulation control that can play an important role in overhead transmission lines. In the early years, insulators were mostly used for telegraph poles. Slowly, a lot of disk-shaped insulators were hung on one end of the high-voltage wire connection tower. It was used to increase the creepage distance. It was usually made of glass or ceramics and was called an insulator. Insulators should not fail due to various electromechanical stresses caused by changes in the environment and electrical load conditions, otherwise the insulators will not have a significant effect and will damage the use and operating life of the entire line.


The main function of insulators is to achieve electrical insulation and mechanical fixation, for which various electrical and mechanical performance requirements are specified. If under the specified operating voltage, lightning overvoltage and internal overvoltage, no breakdown or flashover along the surface; under the specified long-term and short-term mechanical load, no damage and damage; under the specified machine , After long-term operation under electrical load and various environmental conditions, no obvious deterioration will occur; the fittings of insulators will not produce obvious corona discharge under the operating voltage, so as not to interfere with radio or television reception. Because insulators are widely used devices, their connection fittings are also required to be interchangeable. In addition, the technical standards of insulators also require various electrical, mechanical, physical, and environmental conditions to test the performance and quality of the insulators according to different types and conditions of use.


Summary

1) Material:porcelain

2) Class BS: Pw-11-Y  Pw-22-Y   Pw-33-Y   

3)pin type insualators for high voltage

4)safe usage

5)various desigins available

6)fast shipping and great service

7)good quality and reasonable price


Main dimensions and standard particulars
Fig123
Class BSPw-11-YPw-22-YPw-33-Y  
Main Dimensions (mm)H185255320
h32.6532.6532.65
D170205240
d767676
d1
27.7827.7827.78
R1161616

R2161616
Nominal Voltage (kV)152233
Creepage Distance (mm)432673851
Minimum Flashover VoltagePower-frequencyDry (kV)100125140
Wet (kV)6595


110

50% Impulse
Positive
150190210
Withstand VoltageOne minute power- frequencyDry (kV)90110125
Wet (kV)6090100
impulse (kV)140180200
Radio- Influence- Voltage DataTest Voltage to Ground (kV)223044
Maximum RIV at 1000kHz (uV)120001600025000
Cantilever Failing Load(kN)111111
Weight (kg)51013



Similar Product Recommend