FNR12-12 series high voltage AC Vacuum load switch is applied in the three-phase, AC50Hz, rated voltage up to 12KV electric supplying network. The load switch and combination equipments own obvious isolation fractures, can match earthing switch of CO capacity and electric spring mechanism.
Product Details
Introduction
FN12 series high voltage out door circuit breaker can be used for 50HZ 40. 5kv outdoor high voltage electrical equipment.
Attached spring operating structure and electromagnet operating structure can manipulate electric opening and closing in a distance, or accumulate energy for manual operation.
Mainly used in controlling and protection of outdoor power transmission and transformation system of 35kv, also in normal operation and short-circuit protection for all kinds of power grid and frequent operation place.
It has characteristics of well tightness and high temperature endurance, non-combustion and non-exploration, easy mounting, anti-aging and long service life.
No.
project
units
FN12-12
FNR12-12
1
The rated voltage
KV
12
12
2
Rated frequency
Hz
50
50
3
Rated current
A
630
125
4
Rated insulation level
1min power frequency withstand voltage
Against the ground, phase
KV
42
42
The isolation of fracture
KV
48
48
Lightning shock withstand voltage (peak)
Against the ground, phase
KV
75
75
The isolation of fracture
KV
85
85
5
Load switch
KA
20
-
Grounding switch
KA
20
20
6
Load switch
S
4
-
Grounding switch
S
2
2
7
Rated short circuit closing current (peak)
KA
50
-
8
Rated breaking current
Active load breaking current
A
630
-
Closed-loop breaking current
A
630
-
5% active load breaking current
A
31.5
-
Cable charging current
A
10
-
Turn off the no-load transformer capacity
KVA
1250
1250
9
Rated short circuit breaking current (current limiting fuse)