The Fuse Cutout are connected with the incoming feeder of the distribution transformer or distribution lines. These are primary used to protect transformers or lines from short circuits and overloads and switching currents.
Product Details
Features:
1. Small size and light
2. High square wave current impulse
3. Have a good inner management for electric potential
4. Good inner insulation lever to absorb lightning impulse and operation impulse
Technical Data:
Rated Voltage
KV(rms)
3
6
9
10
12
15
18
21
24
27
30
33
36
MCOV
KV(rms)
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17
19.5
22
24.4
27.5
29
Power frequency discharge voltage
≥
KV(rms)
5.5
11
16
18
22
26
33
36
40
45
50
56
61
1.2/50μs Impulse discharge Voltage
≤
KV(rms)
9
18
27
30
36
45
54
63
72
81
90
99
108
8/20μs Lightning impulse residual voltage
≤
KV(crest)
9
18
27
30
36
45
54
63
72
81
90
99
108
Long impulse withstand current2000us
KV(crest)
100
100
100
100
100
100
100
100
100
100
100
100
100
4/10μs High current impulse withstand
KV(crest)
65
65
65
65
65
65
65
65
65
65
65
65
65
Use environment
• Ambient temperature : -40°C~+40°C; • Altitude : not exceed 2000m; • AC System Frequency : 50Hz to 60Hz; • The power frequency voltage applied continuously on the arrester should be less than Continuous Operating Voltage; • Maximum wind velocity : 45m/s; • Earthquake intensity : 7 degree.