TD series vacuum interrupter, is essential part for medium and high voltage breakers.
Product Details
Product description
Volcano main products include vacuum interrupter, embedded pole etc. electrical products. Vacuum interrupter is ceramics type, and the range of voltage is from 1.14kV to 40.5kV, current from 63A to 4000A, rated short circuit breaking current from 2kA to 40kA. Volcanoproducts are complied with relevant national standards and international standards (GB standards and IEC standards). After three large scale technical transformation, introducing advanced production processing equipment from Germany and United States, Volcano has the first-class technology equipment and perfect testing means, and products with the characteristic of standardization, seriation, miniaturization, specialization. For the meantime, Volcano has an experienced R&D team, and a complete , mature R&D program, a special department to organize the development of new products. In order to accurately grasp the development trend of industry technology , Volcano establishes a long-term good relation of cooperation with other well-known domestic and foreign institutions, and carry out technical exchanges with the international well-known enterprises to jointly develop the key products leading the market trend.
Main technical parameter
Parameter item
Unit
Data
Rated voltage
kV
3.6
Rated current
A
200
Rated frequency
Hz
50/60
Rated short-time power frequency withstand voltage(1 min)
kV
18
Rated lightning impulse withstand voltage
kV
28
Rated connecting current
A
2000
Rated breaking current
A
1600
Rated maximum sectional current
A
2000
Rated minimum sectional current
A
40
Rated short-time withstand current
A
2000
Rated short-circuit duration
s
4
Mechanical life
ten-thousand times
100
Rated breaking time AC3
ten-thousand times
15
Rated breaking time AC4
ten-thousand times
6
Contact closing force due to bellows and atomsphere
N
50±10
Force required to hold contact open at full stroke
N
65±15
Circuit resistance at rated contact force
μΩ
≤100
Contact limit erosion
mm
2
Storage life
year
20
Specifications required for matched switchgear
Parameter item
Unit
Data
Rated clearance between open contacts
mm
3±0.3
Average opening speed
m/s
0.6±0.1
Average closing speed
m/s
0.3±0.1
Rated contact pressure
N
100±20
Contact bouncing duration at closing operation
ms
≤3
Closing and opening non-simultaneity of contacts
ms
≤2
Rated contact stroke
mm
1.5±0.3
In mounting, attention should be paid to the following:
a. When operating, guide unite unit must be provided for the interrupter. The coaxality of moving conducting pole and axial line of interrupter must meet the requirement. There should not be torque force applied on the bellow.
b. When mounting, it is forbidden to beat or strike the interrupter envelop with hard things in case crack may occur to cause air leakage.
c. Take care to assure that the conducting pole must be coaxial with interrupter, and that the conducting pole must be vertical on the face of fixed end
d. Take care not to disassemble the interrupter repeatedly to prevent screw from slipping. There should not be twisting on the moving conducting pole and over press on bellow to avoid that any torque force and scratch may occur to bellow to reduce its service life.
e. During mounting, the force applied on the face of both ends should not go beyond the static relief pressure stipulated in the specification.