HFW-40.5 outdoor pole mounted SF6 insulated load break switch is suitable for the distribution network with rated voltage of 12 / 24 / 40.5kV, rated current of 630A, frequency of 50 / 60Hz to open and close the load current and overload current in the power system, which can automatically isolate the fault distribution line section.
Product Details
Summary
Pole-mounted load break switch(pole-LBS) applies up to 36KV 400/630A, 50Hz pole-LBS associated with a state of the art controller. This SF6 gas-insulated switch can corporate with the distribution automation system, and also isolate a faulted section of distribution line from the control center.
A simple pole-mounting arrangement contribute to quick and low cost installation, and the switch can be operated manually with a electronic controller. Electronic controller is contained in a stainless steel cabinet for an all weather environmental conditions. Remote monitoring and control can also be provided mounting wire or wireless modem in a cabinet.
Ambient temperature
Short period peak value:50ºC
Average over a period of 24 hours: 40ºC
Lower limit over 24 hours: -25ºC
Relative humidity: 99%
Maximum altitude:1,000 meter
Main technical specifications
No
Item
Unit
Data
1
Rated voltage
kV
12/20/33
2
Rated current
Hz
50/60
3
Rated insulation level
(with SF6 gas 0.07Mpa)
lightning impulse voltage
kV
75/125/170
Power frequency impulse voltage
kV
42/50/70
5
Rated current
A
630
6
Rated open circuit load current(0.07Mpa//20ºC/h)
A
630
7
Open circuit current under 0 pressure
A
630
8
Rate peak value withstand current
kA
50
9
Rated short-time closing current
kA
50
10
Rated short-time withstand current
kA/s
20/1
11
Rated electric cable charge open circuit current
A
25
12
Rated wire charge open circuit current
A
16
13
Rated closed loop open circuit current
A
630
14
Excitation current
A
21
15
Rated current open circuit times
≥400 times
16
Rated working pressure
MPa
0.07
17
Each operating voltage and resistance
μΩ
≤150
18
Gas relative leakage rate
year
≤1%
19
SF6 gas moisture content
Leave factory relative figure
ppm
≤150
Switch working figure
ppm
≤300
20
Machine stable operation
times
6000
21
Rated operating voltage and assistant loop rated voltage
V
DC220;110
AC 220;110
22
Weight
M type
kg
115
A type
135
Our service