Vacuum contactor uses vacuum interrupter to extinguish arc to frequently connect and cut off normal working current. It is usually used for 6-40.5kV system AC motor in long distance connection and disconnection.
Product Details
JCZ5-7.2/12 KV series high voltage out door circuit breaker can be used for 50HZ-40.5kv outdoor high voltage electrical equipment.
Product description
Attached spring operating structure and electromagnet operating structure can manipulate electric opening and closing in a distance, or accumulate energy for manual operation.
Mainly used in controlling and protection of outdoor power transmission and transformation system of 35kv, also in normal operation and short-circuit protection for all kinds of power grid and frequent operation place.
Highest system voltages Um related to the rated voltages are defined in IEC 60071-1.
These series of VCBs are ceramic pillar type.
Vacuum interrupter is installed in upper part of ceramic insulator.
It has characteristics of well tightness and high temperature endurance, non-combustion and non-exploration, easy mounting, anti-aging and long service life.
Main technical parameter
Type
Unit
JCZ5-630/7.2
JCZ5-630/12
Rated voltage
kV
7.2
12
Rated current
A
160
250
400
630
160
250
400
630
4s thermal stability current
A
160
250
400
630
160
250
400
630
Making capacity
A/100times
1600
2500
4000
6000
1600
2500
4000
6000
Breaking capacity
A/25times
1280
2000
3200
5040
1280
2000
3200
5040
Rated P.F. withstand voltage
kV
28
42
Rated lightning impulse withstand voltage(peak)
kV
60
75
Mechanical life time
times
10,00000
Rated operation voltage
V
AC/DC 110,220,380
Rated operation frequency
times/h
300
Closing time
ms
≤80
Opening time
ms
≤40
Tri-phase asynchronous time
ms
≤2
Clearance between open contacts
mm
5.0±0.5
6.0±0.5
Over travel
mm
1.5±0.5
Each conductive loop resistance
μΩ
≤200