FN18-24 indoor air insulation load break switch and FNR18 fuse combination are designed as key breaking elements for applications in air insulated switchgears and transformer compact substations.Their unique electric arc extinguishing and high switching capacity designs enable then an attractive solution.
Product Details
Structure
FN18 load break switch offers switchgear owners and assemblers the advantages of an assemblers the advantages of an advanced interrupting technology and proven,dependable performance ina a compact design.The switch is available to switchgear assemblers as a building block for metal-enclosed and pad-mounted switchgear application in ratings from 12 upto 24kv.
The standard VACF18 switch includes a steel frame with stand-off insulator,aunique puffe-type arc extinguishing system,an operating mechanism and current-carrying components,including blade-type interrupters with cast hinges and jaw connectors.
Optional accessories and features include avariety of operating handles,a motor operator,auxiliary switches,a shunt trip device,fuse bases,mechanical fuse tripping,grounding switches,mechanical door interlocking and key interlocking.
MODEL DESCRIPTION
Technical Specifications
Item
Data
Rated voltage
12/24kV
Rated current
630A
Rated power frequency
50/60Hz
Rated short-circuit making current
50kA Peak.
Rated peak withstand current
50kA Peak.
Short time withstand current
kAeff.
1 Sec.
31.5/25
2 Sec.
25
3 Sec.
16/20
IEC 62271-105(IEC 420 1990-11)Max.breaking current in co-operation with fuses IEC 62271-105(IEC 420 1990-11)
900/1600A
Max.fuse current(XRNT Fuse)
200A
Rated power frequency withstand voltage (50Hz 1min)