Air Insulated Switch Disconnector

Model
Nature of the Manufacturer
Other
Product Category
Indoor Load Break Switch
Place of Origin
City, Province
Overview
FN18-24 indoor air insulation load break switch and FNR18 fuse combination are designed as key breaking elements for applications in air insulated switchgears and transformer compact substations.Their unique electric arc extinguishing and high switching capacity designs enable then an attractive solution.
Product Details

Structure

  FN18 load break switch offers switchgear owners and assemblers the advantages of an assemblers the advantages of an advanced interrupting technology and proven,dependable performance ina a compact design.The switch is available to switchgear assemblers as a building block for metal-enclosed and pad-mounted switchgear application in ratings from 12 upto 24kv.

    The standard VACF18 switch includes a steel frame with stand-off insulator,aunique puffe-type arc extinguishing system,an operating mechanism and current-carrying components,including blade-type interrupters with cast hinges and jaw connectors.

     Optional accessories and features include avariety of operating handles,a motor operator,auxiliary switches,a shunt trip device,fuse bases,mechanical fuse tripping,grounding switches,mechanical door interlocking and key interlocking.




微信图片_20191119160401


微信图片_20191119160401

MODEL DESCRIPTION

23523


Technical Specifications

ItemData
Rated voltage12/24kV
Rated current630A
Rated power frequency50/60Hz
Rated short-circuit making current50kA Peak.
Rated peak withstand current50kA Peak.
Short time withstand currentkAeff.
1 Sec.31.5/25
2 Sec.25
3 Sec.16/20
IEC 62271-105(IEC 420 1990-11)Max.breaking current in co-operation with fuses IEC 62271-105(IEC 420 1990-11)900/1600A
Max.fuse current(XRNT Fuse)200A
Rated power frequency withstand voltage (50Hz 1min)
-To earth and between phase42/65kV
-Between fracture48/79kV
Impulse withstand voltage (1.2/50μs)
-To earth and between poles75/125kV
-Between fracture85/145kV
Mechanical life200s0cycle

Contact me: Miss Karen Hu

Sales Department

Telephone: +86-

: info@volcano-electrical.com

Webiste: https://www.volcano-electrical.com/