Indoor AC Hv Vacuum Load Switch

Model
Nature of the Manufacturer
Other
Product Category
Indoor Load Break Switch
Place of Origin
City, Province
Overview
FN12-12 and FN12-12R is of three phases indoor use AC high voltage load switch for breaking and making the circuit of 50Hz, 12KV system under rated loading, closed loop current, no-loading transformer, cable charged current and short circuit current. The load switch equipped with earth switch can withstand short circuit current, and m-ainly used in power distribution substation and industrial electrical equipment where three phase closed loop circuit or bottom power supply system for control and protection.
Product Details

Environmental Conditions


1. Ambient temperature: not higher than +40 ºC, not less than -15 ºC (at -30  ºC to allow storage and transportation).
2. Altitude: not exceed 1000m.
3. Earthquake intensity: not more than 8 degree.
4. Wind pressure:≤700pa
5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration

fknjpg

Technical Specifications

Number
Name

Unit
FN12-12DFN12-12D(R)D
1
Rated voltage

KV
12
2
Rated frequency

Hz
50
3
Rated current

A
630125
4
Lighting impulse resisting voltage

KV

To earthing.interphase 75 isolation break 85

5

1min power frequency withstand voltage

KV

To earthing.interphase 42 isolation break 48

6

Rated heat-stability current

KA
20(4S)
7
Rated machine-stability current

KA
50
8
Rated closing current(peak)

KA
5050
9
Rated short-circuit breaking current (prospective value)

KA

31.5
10
Max.critical breaking current

A2S


fuse box characterisitic curve

11

Min.Breaking current

KA


fuse box characterisitic curve

12

Rated transfer current

KA

1.5
13
Max.breaking current(reference value)

KA
1.8
14
Braking no-load transformer capcity

kva
1250
15
Rated cable charging current

A
10
16
Rated power load current breaking times

time

≥100
17
Switch-off time of rated power load current switch on-and-off

S

>0.06
18
Rated transfer current

KA
20(2S)20(2S)
19
Rated transfer current

KA
5050
20
Motor operating power valtage

V

pay 110,220 direct current




Similar Product Recommend