FN12-12 and FN12-12R is of three phases indoor use AC high voltage load switch for breaking and making the circuit of 50Hz, 12KV system under rated loading, closed loop current, no-loading transformer, cable charged current and short circuit current. The load switch equipped with earth switch can withstand short circuit current, and m-ainly used in power distribution substation and industrial electrical equipment where three phase closed loop circuit or bottom power supply system for control and protection.
Product Details
Environmental Conditions
1. Ambient temperature: not higher than +40 ºC, not less than -15 ºC (at -30 ºC to allow storage and transportation). 2. Altitude: not exceed 1000m. 3. Earthquake intensity: not more than 8 degree. 4. Wind pressure:≤700pa 5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration
Technical Specifications
Number
Name
Unit
FN12-12D
FN12-12D(R)D
1
Rated voltage
KV
12
2
Rated frequency
Hz
50
3
Rated current
A
630
125
4
Lighting impulse resisting voltage
KV
To earthing.interphase 75 isolation break 85
5
1min power frequency withstand voltage
KV
To earthing.interphase 42 isolation break 48
6
Rated heat-stability current
KA
20(4S)
7
Rated machine-stability current
KA
50
8
Rated closing current(peak)
KA
50
50
9
Rated short-circuit breaking current (prospective value)
KA
31.5
10
Max.critical breaking current
A2S
fuse box characterisitic curve
11
Min.Breaking current
KA
fuse box characterisitic curve
12
Rated transfer current
KA
1.5
13
Max.breaking current(reference value)
KA
1.8
14
Braking no-load transformer capcity
kva
1250
15
Rated cable charging current
A
10
16
Rated power load current breaking times
time
≥100
17
Switch-off time of rated power load current switch on-and-off