Indoor HV Three-phase Vacuum Load Break Switch

Model
Nature of the Manufacturer
Other
Product Category
Indoor Load Break Switch
Place of Origin
City, Province
Overview
FZN25-12D high voltage vacuum load break switch and fuse combination apparatus are indoor devices with three-phase AC 50Hz and rated voltage of 12kV, which is suitable for industrial and mining enterprise power distribution substation and other occasions. As the protection and control of electrical facilities, it is used for opening and closing load current, closed-loop current, no-load transformer and cable charging current.
Product Details

TB21z6QfpXXXXXSXpXXXXXXXXXX_!!866002174

timg (6)

PRODUCT INTRODUCTION

FZN25-12D high voltage vacuum load break switch(LBS)and FZRN25-12D LBS with fuse combination  are  indoor devices with three-phase AC frequency of 50Hz and rated voltage of 12kV, which is suitable for industrial and mining enterprise power distribution substation and other occasions. As the protection and control of electrical facilities, FZN25-12D is used for opening and closing load current, closed-loop current, no-load transformer and cable charging current.Combine with fuse, the LBS can be used to cut off load current, overload current and short-circuit current,which  has the function of protecting transformer overload, preventing equipment from phase failure, having obvious isolation fracture, and can be equipped with grounding switch and electric operating mechanism with closing capacity to realize remote operation.

FZ(R)N25-12D LBS adopts integral frame assembly structure. In each phase circuit, the dynamic and static contacts are closed in the vacuum tube to form a vacuum arc extinguishing chamber, which is installed on the overall insulation support together with the related conductive body. The upper end of the vacuum arc extinguishing chamber is connected with the isolating switch at the rear through a conductive body to form a conductive circuit. The dynamic and static contacts and conductors of the isolating switch are also installed in the upper and lower integrated insulation support. The whole insulating support is fastened on the metal frame, and the spring energy storage operating mechanism is installed on the side of the metal frame. A detachable fuse device, a fuse and its tripping device are installed on the switch fuse combination apparatus.

The metal frame is provided with grounding cutter arm and spring operating mechanism and interlock. Between the moving and static contacts of the disconnecting switch, there is a plexiglass cover which is high temperature resistant, flame retardant and transparent to effectively guarantee personal safety. The ground static contact is installed at the bottom of the switch and constitutes a LBS with ground switch and a combination of electrical appliances with ground switch.


• FZN25A - 12vacuum load break switch(LBS)

• FZN25A - 12 D vacuum LBS with grounding switch

• FZRN25A - 12  vacuum LBS with  fuse combination 

• FZRN25A - 12 D vacuum LBS and fuse combination with grounding switch


OPERATING ENVIRONMENTAL CONDITIONS

1. Ambient air temperature: upper limit +40℃, lower limit -25℃;

2. Altitude: 1000m or below;

3. Relative humidity: monthly average is not more than 90%.The daily average is not greater than 95%;

4. The surrounding air should not be corroded or inflammable gas, water vapor and other obvious pollution;

5. No regular vigorous exercise;

6. Pollution resistance level: level II.


OUTLINE AND DIMENSION 

TB2Jj0UcFXXXXXzXXXXXXXXXXXX_!!866002174

MAIN TECHNICAL PARAMETER


Item

Unit

FZN25-12D/T630-20

FZRN25-12D/T125-31.5

Rated voltage

kV

12

12

Rated current

A

630

125

Rated short circuit making current

kA

50

50

Rated short circuit breaking current

kA

-

31.5

Rated active load breaking current

A

630

1250

Rated short time withstand current 4s

kA

20

-

Rated peak withstand current

kA

50

-

Rated

Insulation

level

Rated power frequency withstand voltage(1min)

kA

42(fracture48)

42(fracture48)

Rated lighting impulse

withstand voltage(peak)

kA

75(fracture85)

75(fracture85)

Mechanical endurance

times

10000

10000

Rated transfer current(combination)

V

-

2000