The FN(R)18-12(D) is based on a modular principle.The basic unit consists of a frame with insulators and current carrying parts.Two types of operating mechanisms,snap action mechanism type K or stored energy mechanism type A, can be mounted on the frame.Fuse bases type,with or without fuse tripping mechanism,and an earthing switch type,suitable for both direct mounting and free standing components,complete the basic equipment of a switch disconnector.
Product Details
FN(R)18-12(D) series indoor high-voltage switch disconnector is applicable to AC three-phase power system with rated voltage of 12kV and rated frequency of 50Hz for opening and closing load current, closed-loop appliance, no-load transformer and cable charging current, closing short-circuit current, mainly used in ring network or terminal power supply of urban distribution station and industrial electrical equipment for short-circuit protection of control box. It is characterized by advanced design, simple operation, compact structure, small volume, full function, light weight, fast opening and closing speed, high reliability, etc.
The FN(R)18 is based on a modular principle.The basic unit consists of a frame with insulators and current carrying parts.Two types of operating mechanisms,snap action mechanism type K or stored energy mechanism type A, can be mounted on the frame.Fuse bases type,with or without fuse tripping mechanism,and an earthing switch type,suitable for both direct mounting and free standing components,complete the basic equipment of a switch disconnector.
A FN18 load break switch,which interrupts load current up to 1250A,and a small fault current circuit. The FN18 switch combines a fuse base with a current-limiting fuse to create a FNR18 switch,which can break large short-circuit current.It provides protection against a majority of fault types in a modern electric network.Both FN18/FNR18 are designed in accordance with the requirement of the following standards:IEC62271-105,GOST 7717-79,GOST1516.3-96 and CSA Standard No.C22.2,93.
FUNCTIONAL DESCRIPTION
To ensure correct operation for all relevant currents,the FN18/FNR18 ais equipped with a dual arc extinguishing system.As the current is being interrupted,the arc will be exposed to :
1:A current independent air blast which automatically starts at the correnct time during the interrupting process.
2:A current dependent gas blast which occurs when the walls of the arcing nozzles are exposed to the hot arc.
TYPE DESIGNATION
TECHNICAL DATA
Rated voltage
kV
12kV
24kV
Rated current
A
400
630
1250
400
630
1250
Max.rated rated current
A
400
630
1250
400
630
1150
Short circuit making capacity
kA peak
67
67
67
50
50
50
Peak withstand current
kA peak
82
82
82
82
82
82
Short time current 1sec.
kA
31.5
31.5
31.5
25
25
31.5
Mainly active load breaking capacity
A
400
630
1250
400
630
1250
Mainly capacitive breaking capacity
A
150
150
150
80
80
80
Mainly inductive breaking capacity cosφ=0.15
A
16
16
16
16
16
16
Earth fault breaking capacity
A
150
150
150
75
75
75
Capacitive breaking capacity
A
90
90
90
31.5
31.5
31.5
Max. Breaking capacity in co-operation with fuses
A
1600
1600
900
900
Max. Fuse size
A
125
125
80
80
Power frequency withstand voltage
-to earth and between poles
kV
42
55
-acrossisolating distance
kV
45
70
Impulse withstand voltage 1.2/50μs
-to earth and between poles
kV
75
125
-across isolating distance
kV
85
145
Pole distance
mm
150 and 170
235, 250 and 275
Operating angle on the shaft
degree
130
Opening time
ms
40-60
OUTLINE AND DIMENSION OF INSTALLATION
FN18-12D/630 Air 12kV Air insulated LBS with earthing switch