FLN36-12 is a double break rotary load break switch (hereinafter referred to as load switch) with SF6 gas as insulation and arc extinguishing medium, which is suitable for 10kV power distribution system. The load switch is permanently sealed after being charged with 0.4 bar SF6 gas. The switch...
Product Details
FLN36-12 is a double break rotary load break switch (hereinafter referred to as load switch) with SF6 gas as insulation and arc extinguishing medium, which is suitable for 10kV power distribution system. The load switch is permanently sealed after being charged with 0.4 bar SF6 gas. The switch can be installed vertically or horizontally. The typical installation method in the ring main unit is to install a steel partition between the cable room and the busbar room to install it horizontally. This installation isolates the busbar from the cable connector to meet the most stringent safety requirements for operation and maintenance.
Daily average relative humidity: < 95% monthly average relative humidity: < 90%
Daily average vapor pressure: < 2.2 × 10-3mpa monthly average vapor pressure: < 1.8 × 10-3mpa
2 Altitude: not more than 1000m;
3 The seismic intensity shall not exceed 8 degrees;
4 The place of use shall be free from water dripping, frost, condensation, inflammable and explosion hazards, chemical corrosive gas and violent vibration.
STRUCTURAL CHARACTERISTICS
1.FLN36-12 load switch adopts double break and rotary moving contact, with the following three states: closing, opening and grounding.
2.The load switch adopts SF6 as arc extinguishing and insulating medium, and the switch is made of epoxy resin cast upper and lower shells with good insulation performance.
3.Good safety performance.In case of internal arcing, there is a structural weak point at the rear of the shell, it will be opened, and then the arc relief valve on the top of the switchgear will be opened and the overpressure air flow will be directed outside the switchgear.
4.FLN36-12 type load switch and operating mechanism are arranged in the detachable upper unit of the switchgear, which can easily change the LBS type switchgear into the load switch + fuse combination type,and vice versa.