The KYN28 type indoor metal clad air insulated switchgear (hereinafter referred to as switchgear) is a set of complete distribution devices suitable for rated current up to 24kV, three-phase AC 50 Hz, single bus and single bus sectional system. It is mainly used for power transmission of middle/small generators in power plants;power receiving,transmission for substations in power distribution and power system of factories, mines and enterprises,and starting of large high-voltage motor,etc.,so as to control,protect ......
Product Details
Product introduction
The KYN28 type indoor metal clad air insulated switchgear (hereinafter referred to as switchgear) is a set of complete distribution devices suitable for rated current up to 24kV, three-phase AC 50 Hz, single bus and single bus sectional system. It is mainly used for power transmission of middle/small generators in power plants;power receiving,transmission for substations in power distribution and power system of factories, mines and enterprises,and starting of large high-voltage motor,etc.,so as to control,protect and monitor the system. The switchgear conforms to IEC298 and GB3906 Standards.
The enclosure of KYN28 is made of aluminum zinc steel plate by numerical control, with high dimensional accuracy, short production cycle, good mechanical strength and beautiful appearance. Bus room, VCB manual control room, cable room and relay room are separated by metal plate. Flexible operation for handcart movement, clear position instruction, the earthing switch allow to making short circuit current and creditable mechanical interlock. It is suitbale for many kinds of handcart circuit breaker such as VD4, VS1 and VHY1-12 etc. The switchgear is air insulated, and the door ofVCB has the function of explosion-proof . Theswitchgear adopts air insulated design and the door of circuit breaker have the function of anti- explosion, tested byinternal electric arcing fault, without any welding contacts on the panel. In order to meet the requirements of wall hanging and front-end maintenance, the switchgear is equipped with a special current transformer, and the operator can maintain and inspect it in front of the cabinet.
Service environment a) Air temperature: Maximum temperature: +40℃; Minimum temperature:-15℃
b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level: Maximum installation altitude: 1000M.
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake
Technical data
No
Item
Unit
Parameter
1
Rated voltage
KV
3.6,7.2/12
2
Rated frequency
Hz
50
3
Rated current of breaker
A
630,1250,1600,2000,2500,3150
4
Rated breaking active load current
A
630,1250,1600,2000,2500,3150
5
Rated closed loop breaking current
KA
20,25,31.5,40
6
Rated current under the cable charging breaking current
KA
50,63,80,100
7
Rated short-circuit closing current(peak)
KA
20,25,31.5,40
8
Rated short-circuit breaking current
KA
50,63,80,100
9
Rated insulation level
1 min frequency withstand voltage
Pole,the pole pair
KV
24,32,42
break between
KV
24,32,48
Lighting impulse withstand voltage(peak)
Pole,the pole pair
KV
40,60,75
break between
KV
46,70,85
10
Degree of protection
KV
Enclosure IP4X,compartment,circuit breaker door open when IP2X
1. Framework2. Hinge3. Middle Hinge4. Rear Plate5. Top Cover of Cable Compartment6. Post Insulator7. Busbar Bushings8. A-phase Busbar9. B-phase Busbar10. C-phase Busbar 11. Top Cover of Busbar Comparment12. Top Cover of VCB Compartment13. Door of Instrument Compartment14. Contact Box15. Fixed Contact16. Fixing Plate of Aerial Socket17. Left Plate of VCB Compartment18. Right Plate of VCB Compartment19. Door of VCB20. Vacuum Circuit Breaker 21. Interlock & Shutter System22. Earthing Switch Interlock23. Left Plate of Cable Compartment24. Right Plate of Cable Compartment25. Door of Cable Compartment26. PT handcart27. Earthing Busbar28. Branch Busbar29. Current Transfarmer