The XGN2-12 fixed metal enclosed switchgear is suitable for the distribution system of residential buildings, high-rise office buildings, parks, industrial and mining industries. The switchgear is suitable for 3-10kV single bus, single bus with bypass system as a complete set of high-voltage equipment to receive and distribute electric energy.
Product Details
The XGN2-12 fixed metal enclosed switchgear is suitable for the distribution system of residential buildings, high-rise office buildings, parks, industrial and mining industries. The switchgear is suitable for 3-10kV single bus, single bus with bypass system as a complete set of high-voltage equipment to receive and distribute electric energy. The double bus structure can be derived. The switchgear can be used for the breaking of rated load current and no-load current of transformer, as well as the breaking of overhead line, cable line and capacitor bank capacitance current of a certain distance.
It adopts ZN28-12 or VS1-12 series vacuum circuit breaker as the main switch, the isolating switch adopts GN30-12 or GN22-12 series, and the instrument transformer adopts full insulation structure.The switchgear has reliable five prevention interlock.
Structural characteristics
The switchgear is a metal enclosed box structure. The frame of the switchgear is welded by angle steel. The switch cabinet is divided into a circuit breaker chamber, a bus bar, a cable room and a relay room by steel plates, and the operation of the main components in the cabinet can be observed through the observation windows and lighting lamps on the facade. In order to improve the technical performance of the switchgear, the main components are redesigned (such as circuit breaker, rotary isolating switch, etc.). According to the layout of the cabinet, relay can be installed in the relay room, and signal relay, indicating instrument and signal lamp can be installed on the door. The change-over switch is installed in the operation room. The bus room is at the back and the cable room is at the bottom, so users can easily connect the wires The circuit breaker room is in the front of the cabinet, which facilitates the maintenance of the main switch of the switchgear.
Ambient condition
1.Ambient temperature upper limit and lower limit are respectively +40℃ and -20℃; 2.Relative humidity: daily average value is not more than 95%, while the monthly average value is not more than 90%; 3.Altitude is not more than 1000m; 4.Places without fire, explosion, serious pollution, chemical corrosion and violent vibration.
Technical parameters of XGN2-12 fixed metal-enclosed switchgear
Items
Parameters
Rated voltage (kV)
3.6, 7.2, 12
Rated current (A)
630 - 3150
Maximum working current (A)
630, 1000, 1250, 2000, 2500, 3150
Rated short-circuit breaking current (kA)
20, 31.5, 40
Rated short time withstand current (kA)
20, 31.5, 40
Rated peak withstand current (kA)
50, 80, 100
Rated making current (kA)
50, 80, 100
Thermal stabilization time (s)
4
Protection degree
IP2X
Weight (kg)
400 - 700
Overall size (width × depth × height) (mm)
1100 × 1200 × 2650 (1250 A and below)
1200 × 1200 × 2650 (1250 A above)
Technical parameters of ZN28-12 vacuum circuit breaker
Items
Parameters
Rated voltage (kV)
12
Rated frequency (Hz)
50
Rated current (A)
1250, 2000, 2500, 3150
Rated short-circuit breaking current (kA)
20, 31.5, 40
Rated making current (kA)
50, 80, 100
Rated short-time withstand current (kA)
20, 31.5, 40
Rated peak withstand current (kA)
50, 80, 100
Thermal stable time (s)
4
Mechanical life (Times)
10000
Vacuum interrupter vacuum degree (Pa)
≥ 6.6 × 102
Arcing time (ms)
≤ 20
Rated short-circuit breaking current breaking times (Times)