SRM16-12kV series SF6 gas insulated ring main unit is installed on a galvanized plate frame, and the switch units are all in SF6 gas tank , which is made of corrosion-resistant and non-magnetic 3mm thick stainless steel plate. SF6 gas tank is a sealed pressure system which can...
Product Details
SRM16-12kV series SF6 gas insulated ring main unit is installed on a galvanized plate frame, and the switch units are all in SF6 gas tank, which is made of corrosion-resistant and non-magnetic 3mm thick stainless steel plate.SF6 gas tank is a 'sealed pressure system' which can operate for 20 years under normal working environment. The normal working pressure of SF6 gas is 0.15 ~ 0.4bar. There is a pressure release device installed with the gas tank, which can ensure the physical strength to release from the bottom or the rear when the pressure is too high.
◆ SWITCH UNIT
The load break switch adopts the coaxial rotation double break-point mode, and carries out kinetic energy operation by cooperating with the operation hole and sliding plate. At any moment, the switch can only be in one of the three states of "closing, opening and grounding", so as to completely avoid misoperation.
◆ OPERATING MECHANISM
The operating mechanism of the switch is installed in the front of the box, which is treated by special process, rust proof, convenient for manual operation and maintenance, and easy to realize electric operation.
◆ CABLE ROOM THAT REALLY MEETS THE NEEDS
The cable connection room has a large space, and the sleeve is of standard design, which realizes the coordination with all European standard cable plugs. Normally, each load break switch unit can be connected to the 1~3 return line, and the special design type can be connected with the 4~6 return line. The vacuum circuit breaker unit can be connected with 1~2 outgoing lines.
◆ PRESSURE RELIEF DEVICE
The pressure relief device and the cable room are separated by metal plates. If the pressure in the air box is too high, the explosion-proof diaphragm in the device will break to release the pressure.
◆ CABLE CONNECTION
The international standard general specification sleeve is selected to facilitate the user to select the corresponding cable accessories.
◆ ARRESTER CONNECTION
The load switch unit can be equipped with T-shaped back plug type silicon rubber fully sealed metal zinc oxide arrester. When the number of cable circuits is large and the space is not enough, the π - shaped back plug arrester can be used.
◆ INTERLOCKING MECHANISM
The interlock mechanism inside the switch can effectively prevent misoperation and ensure that the cable room can only enter when the switch is in the "grounded" state.
◆ AUXILIARY SWITCH
Load break switch and grounding switch can be equipped with auxiliary switch which can synchronously reflect the switch position state as required.
◆FUSE
The fuse is easy to replace. The fuse is placed in the insulating tube which is located in the metal gas box of SF6.