Welcome Customer !

Membership

Zhejiang Volcano electrical technology Co., Ltd
Free Member ·1YRS
Other

Main Products: 断路器

Xwboo>Products

Zhejiang Volcano electrical technology Co., LtdFree·1YRS

  • E-mail

    info@volcano-electrical.com

  • Phone

    +86-577-61668058

  • Address

    Building 2,59, Weishiliu Road, Economic Development Zone, Chengdong Street, Yueqing, Zhejiang, China

Contact Now

Solid Sealed Pole For Vcb

Model
Nature of the Manufacturer
Other
Product Category
Vacuum Interrupter
Place of Origin
City, Province
Overview
The solid sealed pole is mainly used in vacuum circuit breakers with rated voltage of 12kV, 24kV and 40.5kV.The product adopts epoxy resin automatic pressure gel forming technology, first vulcanizing a layer of silicone rubber on the surface of the vacuum interrupter, then assembling the vacuum...
Product Details

The solid sealed pole is mainly used in vacuum circuit breakers with rated voltage of 12kV, 24kV and 40.5kV.The product adopts epoxy resin automatic pressure gel forming technology, first vulcanizing a layer of silicone rubber on the surface of the vacuum interrupter, then assembling the vacuum interrupter and the conductive elements of the vacuum circuit breaker, and then placing the mold into the epoxy resin material to solidify and form the whole pole of the vacuum circuit breaker into an integral part. It replaces the insulation support and mechanical support on the original vacuum circuit breaker, greatly reduces the parts and volume of the vacuum circuit breaker, and is conducive to the miniaturization of the switch cabinet. It has the advantages of easy installation, maintenance free, small volume, and more stable and reliable pressure.


WORKING CONDITION 

  • -The ambient temperature shall be within the range of - 15 ℃ - + 40 ℃, and the daily average temperature shall not exceed + 35℃;

  • -The daily average relative humidity shall not exceed 95% and the monthly average relative humidity shall not exceed 90%;

  • -The altitude shall not exceed 3000m;

  • -The seismic intensity shall not be greater than 8 degree horizontal acceleration.

  • -The surrounding air shall not be polluted by erosion and combustible gas, steam, etc.

MAIN TECHNICAL DATA


Data


Unit


Value


1

Rated voltage

kV

12


2

Rated current

A

2000

2500


3

Rated frequency

Hz

50


4

Rated short-circuit breaking current

kA

40


5

Operations of short-circuit breaking current interruption

times

30


6

Rated short-circuit making current

kA

100


7

Rated peak withstand current

kA

100


8

Rated short-time withstand current(4s)

kA

40


9

Rated single capacitor bank breaking current

A

630


10

Rated back-to-back capacitor breaking current

A

400


11

Short-time(1min) power-frequency withstand voltage

kV

42


12

Lightning impulse withstand voltage(peak)

kV

75


13

Circuit resistance at rated contact force

μΩ

≤25


14

Mechanical life

times

30,000


15

Contact closing force due to bellows and atmosphere

N

120±50


16

Counterforve at rated contact stroke

N

200±50


17

Contact limit erosion

mm

3


18

Shelf life

YEAR

20


19

Partial discharge

pC

≤1


20

Rated operating sequence

0-0.3s-co-180s-co



zn63(vbm7)-12-fixed-indoor-vacuum-circuit-breaker-1