Semi-closed Dry Voltage Transformer

Model
Nature of the Manufacturer
Other
Product Category
Voltage Transformer
Place of Origin
City, Province
Overview
​JDZ-10kV type are single phase double coil,semi-enclosed indoor voltage transformer of epoxy resin casting full insulation structure.
Product Details

半封闭

JDZ-10kV type are  single phase double coil,semi-enclosed indoor voltage transformer of epoxy resin casting full insulation structure.The core is made of high quality silicon steel sheet. All windings are cast by epoxy resin, which has characteristics of  good insulation, impact resistance, mechanical pressure resistance, and can protect the winding from moisture. 

The mark of the outlet terminal of primary winding is A, X; The marks of the terminal of the secondary winding lead wire are a and x, which are clearly marked on the pouring body next to the grounding mark on the clamp. The earthing bolt is provided for earthing and the lower bracket is provided for installation. The whole structure is compact and easy to use.

The voltage transformer is suitable for 12kV power systems to turn high voltage into low voltage and large current into small current for measurement or protection systems. In order to achieve standardization and miniaturization of measuring instruments, protection equipment and automatic control equipment.

Characteristic of structure

1. Epoxy resin semi-closed full insulation structure .

2. Core volts quality cold-rolled silicon steel sheet piled.

3. Small size, light weight, limited installation space

4. All windings are fully cast in epoxy resin with excellent insulating properties
    Impact resistance and mechanical stress.

Environment condition

l Altitude:should not exceed 1000m.

l Ambient temperature:-5ºC~+40ºC.

l Air relative humidity:≤85%.

l Air relative site:indoor.

 

Technical parameters(JDZC)

 Type

Rated voltage ratio

Accuracy class and rated output

VA COSφ=0.8

Rated insulation level(KV)

0.2/3

0.5/3

0.5/0.5

0.5/3P

0.5/6P

JDZC-6

6/0.1/0.22KV

30/300

50/300

50/80

50/500

50/800

7.2/32/60

JDZC-10

10/0.1/0.22KV

30/300

50/300

50/80

50/500

50/800

12/42/75