Medium Voltage Outdoor Voltage Transformer

Model
Nature of the Manufacturer
Other
Product Category
Voltage Transformer
Place of Origin
City, Province
Overview
This series of voltage transformers includes versions: JDZW-35, JDZFW-35, JDZXFW-35.They are suitable for outdoor power systems of rated frequency of 50/60Hz and rated voltage of 35kV and below for electrical energy measurement, voltage monitoring and relay protection.
Product Details

This series of voltage transformers includes versions: JDZW-35, JDZFW-35, JDZXFW-35. The product is an outdoor single-phase dry type voltage transformer.It adopts fully enclosed semi-insulated casting structure, which is cast by arc insulation, UV resistant and aging resistant outdoor insulation resin.They are suitable for outdoor power systems of rated frequency of 50/60Hz and rated voltage of 35kV and below for electrical energy measurement, voltage monitoring and relay protection.This series voltage transformer can be installed in any position and installed in any direction.The products are designed in accordance with Standards GB1207-2006.

35DRY

35

Technical Date


Type

Rated voltage ratio (kV)

Accuracy class

(VA)

Rated output

Limited output

Rated insulation level(kV)

 

 (VA)

 (VA)

JDZW-35

35/0.1
35/0.1/0.22

0.2
0.5
1

75
150
250

1000

40.5/95/200

JDZXW-35G

35/√3/0.1/√3/0.1/3

0.2/6P(3P)
0.5/6P(3P)
1/6P(3P)

75/100
150/100
250/100

35/√3/0.1/√3/0.1/√3/0.1/3

0.2/0.2/6P(3P)
0.2/0.5/6P(3P)
0.5/0.5/6P(3P)

30/30/100
30/60/100
60/60/100

2×500

image

Precautions for use of voltage transformer

1. The PT shall be tested and inspected according to the items stipulated in the regulations before putting into operation. For example, polarity measurement, connection group, shaking insulation, nuclear phase sequence, etc.

2. The capacity of the load connected to the secondary side of the PT should be appropriate, and the load connected to the secondary side  should not exceed its rated capacity, otherwise, the error of the PT will increase and it is difficult to achieve the accuracy of measurement.

3. Short circuit is not allowed on the two side of PT. Due to the small internal impedance of the PT, when the secondary circuit is short circuited, a large current will appear, which will damage the secondary equipment and even endanger personal safety. The PT can be equipped with fuse at the secondary side to protect itself from damage due to short circuit at the secondary side. Where possible, fuses shall also be installed at the primary side to protect the high-voltage grid from endangering the safety of the primary system due to the fault of the high-voltage winding or lead wire of the transformer..

4. In order to ensure the safety of people when they contact the measuring instrument and relay, the secondary winding of the PT must be grounded a little. Because after grounding, when the insulation between the primary and secondary windings is damaged, it can prevent the instrument and relay from endangering personal safety with high voltage.