Welcome Customer !

Membership

Qingxian Zeming Langxi Electronic Devices Co., Ltd.
Free Member ·1YRS
NanJing,JiangSu
Manufacturer

Main Products: Current Transformer|Voltage Regulating Transformer

Xwboo>Products

Qingxian Zeming Langxi Electronic Devices Co., Ltd.Free·1YRS

  • E-mail

    zm@zeming-e.com

  • Phone

    86-25-52601870

  • Address

    R208, Block B, Geminis Building, 30# Tulip RD, Yuhuatai Dist, 210012, Nanjing city, Jiangsu Province, China

Contact Now

φ45 5000:1 800A Split core current transformer

Model
Nature of the Manufacturer
Manufacturer
Product Category
Split Core Current Transformer
Place of Origin
City, Province
Overview
Split core current transformer Application and Features 1. Measurement and protection for instruments 2. General measurement and protection in power systems for highly mobility or space-constrained or uninterrupted power systems. 3. With the split core structure, easy to install, remove, and operate without disconnecting the measured primary conductor. 4. beautiful appearance, small size and light weight .
Product Details

Structural Parameters

图片1


       Front View Lateral View

                                                    “*" Same polarity


Product Description

all ptoducts1

Details

Product characteristics and application:

 

Rated input current

800A

Accuracy class

0.5

Rated output current

160mA

Installation

Split core type

Turns ratio

5000:1

Operating

temperature

-25℃~+75℃

Operating current

0~960A(10Ω)

Relative humidity

≤95%

Case material

Nylon

Operating

frequency

50HZ/60HZ

 

(1) Dielectric strength:power frequency between primary winding and secondary winding 2.5KV/min, no breakdown flash-over phenomenon,leakage current<1mA;

(2) Insulation resistor:Between primary winding and secondary winding ≥1000MΩ/500Vdc


 

Error Range:

 

Input current

5

20

100

120

Ratio error (±%)

±0.75

±0.5

±0.5

±0.5

Phase error (′)

≤30

≤20

≤20

≤20

 

Reliability test:

 

No.

Items

contents

condition

Application standard

1

High temperature

storage

Durability test, long time high temperature

storage.

85 ℃ 48hours

Corporate standard

2

Low temperature

storage

Durability test, long time low temperature

storage.

-40 ℃ 48 hours

Corporate standard

3

High temperature

operation

Durability test, long time in the state of high

temperature power.

75 ℃ 16 hours

 

Corporate standard

4

Low temperature

operation

Durability test, long time in the state of low

temperature power.

-25℃ 16 hours

Corporate standard

5

High temperature/high humidity storage

Durability test, high temperature and high humidity storage for a long time.

60 ℃ , 90 %RH 48 hours

Corporate standard

6

High temperature/high humidity operation

Durability test, long time in high temperature and high humidity power on state.

40 ℃, 90 %RH 16 hours

Corporate standard

 

7

 

Cold and hot cycle shock

Durability test in electrified and cold and hot cycle condition. 25℃ 5min. 1 Cycle 70℃ 30min

-20℃ 30min

 

-20°C / 70°C 10 Cycle

 

Corporate standard

Mechanical test

 

 

8

 

 

Vibration test

 

Durability testing, transportation and use in the state of vibration.

Frequency:10~55~ 10Hz amplitude:1.5mm Cycle:1 Log/min time: X.Y.Direction 0.5 hour

each

 

 

Corporate standard

 

Label Content:

1