Welcome Customer !

Membership

Qingxian Zeming Langxi Electronic Devices Co., Ltd.
Free Member ·1YRS
NanJing,JiangSu
Manufacturer

Main Products: Current Transformer|Voltage Regulating Transformer

Xwboo>Products

Qingxian Zeming Langxi Electronic Devices Co., Ltd.Free·1YRS

  • E-mail

    zm@zeming-e.com

  • Phone

    86-25-52601870

  • Address

    R208, Block B, Geminis Building, 30# Tulip RD, Yuhuatai Dist, 210012, Nanjing city, Jiangsu Province, China

Contact Now

2000:1 PCB mounting current transformer 0.2class

Model
Nature of the Manufacturer
Manufacturer
Product Category
Mini Precision Current Transformer
Place of Origin
City, Province
Overview
ZEMCT131 mini Precise current transformer. Small size, high accuracy, good consistency,Applied to the power frequency 50(60)Hz multifunction meter
Product Details

Structural parameter

ZEMCT131 Precise current transformer

Small size, high accuracy, good consistency,Applied to the power frequency 50(60)Hz 

multifunction meter

Structural parameter:

图片1 

                                           Input: 1、2pins,output : 3、4pins                          Same plority (*)

 

                                        Front view                                                            Bottom view


Main technical parameters

Model  

ZEMCT131

Rated   input current

5A

Rated   output current

2.5mA

Turns   ratio

2000:1

Phase   angle error

≤20'(Input 1A,sampling resistor 100Ω)

Continuous   current range

0~6A

Linearity

0.2%(5%dot~120%dot)

Permissible   error

 -0.2%≤f≤+0.2%(Input 1A,sampling resistor 100Ω)

Isolation   voltage

3000V

application

Accurate measurement of current and   power

Installation

PCB   mounting(Pin length>3mm)

encapsulation

Epoxy

Operating   temperature

-40℃~+85℃


Instructions for use

ZEMCT131-

                    Figure Ⅰ                                                                              FigureⅡ

1. The typical usage of the product is for the active output ( Figure Ⅰ) . R is a sampling resistor.

2. The product can be directly through the resistance sampling , easy to use ( FigureⅡ).