WENZHOU MINGZHE ELECTRIC CO LTDFree·1YRS
dayday@mignzhee.com
88 Xiangyun East Road,Yueqing City ,Zhejiang ,China

Brief Introduction:
XGN15-12(L)/T630-25 0r XGN15-12(L . R)/T100-31.5 box-type fixed AC metal enclosed switchgear is mainly used for looped network power supply or biradial power supply of electric power system with 3-phase ,AC 50Hz and rated voltage 10KV. It also can be used for terminal power supply as the control device of electric energy and protection device of utilization equipment. More over, it also can be suitable for this switchgear to be installed in the box substation, especially compact box substation.
Service Environmental Condition:
⑴ Altitude: .< l000m
⑵Ambient temperature: -25aC ~ +400C
⑶Relative humidity: The daily average value is not more than 95% and the monthly mean value is not more than 90%.
⑷The surrounding air shall not be polluted by corrosive gas and flammable gas as well as water vapor and so on obviously.
⑸. No location of recurrent strenuous vibration
The main technical parameters:
NO. | Item | Unit | Technical parameters | ||||
XGN15-12(F) | XGN15-12(F,R) | ||||||
1 | Rated voltage | KV | 12 | ||||
2 | Rated Frequency | Hz | 50 | ||||
3 | Rated insulation level | 1 min power frequency withstand voltage | Kv | To-Grounding and phase -to-phase42;Isolating distance48 | |||
Lighting impulse withstand voltage(peak) | kv | To-Ground and phase-to-phase 75; | |||||
4 | Rated current of main bus | A | 630 | ||||
6 | Rated current | A | 630 | 125 | |||
7 | Rated closed loop breaking current | A | 630 | ||||
8 | Rated charging breaking current | A | 10 | ||||
9 | Rated transfer current | A | 1700 | ||||
10 | Breaking no-load transformer capacity | KVA | 1600 | ||||
11 | Rated making current(peak) | KA | 63 | ||||
12 | Rated short-time withstand current | KA | 25 | ||||
13 | Rated peak withstand current | KA | 63 | ||||
14 | Rated short-circuit breaking current | KA | |||||
15 | Peak withstand current of ground circuit(prospective) | KA | 63 | 31.3(Prospective) | |||
16 | Short-time withstand current of grounding circuit | KA | 25 | ||||
17 | Fuse model | S□LAJ | |||||
18 | Rated voltage of auxiliary circuit | V | DC220 110 AC220 110 | ||||
19 | IP Code | IP3X | |||||
20 | Mechanical life | Load switch (times) | Times | 5000 | |||
Earthing switch(times) | Times | 2000 | |||||
Cabinet type:
⑴.cabinet of SF6 load switch incoming line cell

②cabinet of SF6 load switch with fuse single line drawing