Queen Star Series 10K - 80KVA

Model
Nature of the Manufacturer
Manufacturer
Product Category
High Frequency Online UPS
Place of Origin
City, Province
Overview
DSP + IGBT technology.Output power factor 0.9.Active power factor correction in all phases.Emergency power off function (EPO).
Product Details

Online UPS Queen Star Series 10K-80KVA  (3ph in/3ph out)

 

Key Features:

  • True double-conversion.
  • DSP technology guarantees high performance.
  • Output power factor 0.9.
  • Active power factor correction in all phases.
  • 50Hz/60Hz frequency converter mode.
  • Accepts dual-mains inputs.
  • Generator compatible.
  • SNMP+USB+RS-232 multiple communications.
  • 3-stage extendable charging design for optimized battery performance.
  • Adjustable battery numbers.
  • Maintenance bypass available.
  • Optional N+X parallel redundancy.
Model33Q10KL33Q 20KL33Q 30KL33Q 40KL33Q 60KL33Q 80KLComments
Input
Input voltage
Rated voltage380VAC/220VAC380VAC 
Phasethree phase with ground 
Turn on voltage range(120±5~274±5)VAC(207±9~475±9)VAC 
Bypass voltage range(60±5~300±5)VAC(105±9~518±9)VACCould be adjusted by software.
Bypass60VAC~220VAC(default 60VAC)105VAC~380VAC 
low loss(default 105VAC)
Bypass low comebackLow loss +5VACLow loss +17VAC 
Bypass high loss220VAC~300VAC(default 300VAC)380VAC~475VAC 
(default 475VAC)
Bypass high comebackHigh loss -5VACHigh loss -17VAC 
Line low loss(120±5) VAC /(140±5) VAC(207±9) VAC /(242±9)VACload≤50%
/comeback(140±5) VAC /(160±5) VAC(242±9) VAC /(276±9)VAC50%<load ≤90%
 (160±5) VAC /(175±5) VAC(276±9) VAC /(302±9)VACload>90%
Line high loss/comeback(275±5)VAC/(260±5)VAC(475±9)VAC/(449±9)VAC 
Input frequency
Rated frequency50Hz 
Frequency(40~49) ±0.2Hz(default:46Hz)Could be adjusted by software.
low loss
FrequencyFrequency low loss +0.5Hz
low comeback
Frequency(51~60)±0.2Hz(default:54Hz)
high loss
Frequency high comebackFrequency high loss -0.5Hz
Input power factor
Input power factor> 0.9933Q 10-40KL:220VAC,full R load
33Q 60-80KL: 380VAC,full R load
GeneratorSupport generator inputGenerator rating≥2*UPS rating
Input current
Rated current14A28A42A67A80A105A 
Input THDI<= 10% 
Output protection
Rating protection32A50A60A80A100A125A 
BreakerBreakerBreakerBreakerBreakerBreaker
Output power
VA/watt10KVA/8KW20KVA/16KW30KVA/24KW40KVA/32KW60KVA/80KVA/ 
48KW64KW
Rated voltage220VAC380VACSine wave
Voltage range200/208/220/230/240VAC345/359/380/397/415 VAC33Q 10-40KL: Could be adjusted by software. 10% derating for 208VAC/200VAC.
33Q 60-80KL: Could be adjusted by software. 10% derating for 345VAC/359VAC.
Voltage regulation±1% 
Voltage distortion≤5%≤10%Full RCD load
≤3%Full R load
DC offset≤200mV 
Transient response≤9%R load 0%~100%~0%
≤6%R load 20%~100%~20%
Transient recovery≤60ms voltage recovery to 90%Full RCD load
Bypass outputYES 
before turn-on
Crest ration3:1 
Output frequency range
Normal mode1,Same as input frequency(46Hz~54Hz) 
2,50Hz(Input frequency>54Hz or Input frequency<46Hz)
Battery mode(50±0.1) Hz 
Slew rate1 Hz/Sec 
Efficiency
Normal  mode> 93%> 90% 
Battery mode> 90%> 90% 
Overload
Normal modeOverload warning only105%±5%≤load
/battery mode1min,then transfer to bypass and alarm.105%±5%
 30S,then transfer to bypass and alarm.125%±5%
 300mS, then transfer to bypass and alarm.load>150%±5%
Automatically retransferYES 
Short protection
Normal/YES 
battery mode
Transfer time
Normal to battery mode0mS 
Battery to normal mode0mS 
Normal to bypass mode<4mS0mS 
Bypass to normal mode<4mS0mS 
Battery and charger
Battery
Rated voltage192VDC240VDC192VDC*2192VDC*2480VDC 
Type/Rating      
Battery quantity162016*216*240 
Backup time      
Protection
Low alarm voltage /comeback voltage(180.8V±4V)/ (188.8V±4V)(226V±4V)/ (236V±4V)(180.8V±4V)/ (188.8V±4V)(226V±4V)/ (236V±4V)(452V±4V)/ (472V±4V)33Q 30KL use two
Shutdown voltage/ comeback voltage160V±4V/168V±4V(200V±4V)/ (210V±4V)160V±4V/(200V±4V)/ (210V±4V)(400V±4V)/ (420V±4V) 
168V±4V
DC protection
Overcharge protection/ comeback voltage(249.6V±4V)/(312V±4V) (270V±4V)(249.6V±4V)/ (216V±4V)(312V±4V) (270V±4V)(624V±4V) (540V±4V) 
(216V±4V)
Leakage current< 500uA 
Over discharge protection14.5h Could be set by software
Battery test
Battery weakYES 
Battery faultYES 
Charger
Output voltage(219.2±3)VDC(277±3)VDC(219.2±3)VDC(277±3)VDC(554±3)VDC 
Charge timeDepends on the external battery capacity 
Charge current7.5A6A5A4A10A 
Interface
Alarm silenceYES 
DC powerYES 
turn-on
Automatically retransferYES 
Audio alarm
Battery modeBeep/4s 
Battery low/Beep/1s 
charger fault
UPS faultContinue beep 
OverloadBeep/1s 
Bypass modeBeep/2Min 
L/N inverseBeep/2Min 
Communication
RS232 interfaceYES 
Intelligent slotYES 
Monitor softwareAppending with UPS 
Cooling
Force air cooling 
Display
LCD/LED displays UPS status
Environment
Work temperature0℃~40℃ 
Altitude<1000m 
Audible noise≤60dB 
Storage temperature-15℃~45℃ 
Work humidity20%~95% 
Standard
EMS
ESDIEC61000-4-2Level4
RSIEC61000-4-3Level3
EFTIEC61000-4-4Level4
SurgeIEC61000-4-5Level4
EMI
ConductedEN55022Class A
RadiatedEN55022Class A
Safety
SafetyGB4943-2001/IEC62040-1 
Machinery features
Size
Outline dimension and net weight
L*W*H (mm)710*260*717840*515*1135 
Net weight(Kg)45/9350/98  195208 
Optional functions
60Hz  OptionalSet by software
Converter mode  OptionalSet by software
ECOOptionalOptionalAvailable and set by software
EPOOptionalOptional 