| Model | LP33 20~30Kva | LP33 40~60Kva | LP33 80~100Kva | LP33 120~200Kva |
| Transference | 0ms Cutless |
| Technology | True double-conversion online technology, conversion performed by IGBT |
| Input | Voltage | 3*220 / 380Vac ± 25% |
| Frequency | 50Hz ± 15% |
| Conductors | Three phrases + N +E |
| Ootput | Voltage(Delectable) | 3*220 / 380Vac ± 1% (More voltage can be selected) |
| Frequency | 50Hz ± 0.1% |
| Waveform | Pure sine wave generated by high frequency PWM inverter |
| Harmonic Distortion | <2% linear load / <5% nonlinear load |
| Crest Factor | 3:1 |
| Power Factor | ≥0.9 |
| Overload Regulation | Self-Transference to UPS |
| Voltage Regulation | Load balance : ±1% |
| Overload Capacity | 125% for 12 minutes / 150% for one minute |
| Conductors | Three phrases + N +E |
| Battery | Type | Maintenance-free sealed lead-acid battery, 12V*32 bars; 120Kva, 160Kva and 200Kva, 12V*40 bars |
| Full Load Autonomy | 3 to 15 minutes. Extended-range capability |
| Typical Recharge Time | 4 ~ 8 hours, 90% |
| Battery Handy | Autotest.Transfer point adjustable battery and alarm setting |
| Battery Protection | Fuse protection, Battery switch, Temperature compensation, Regular inspection, Software protection,Overvoltage tripping. |
| Rectification | Software protection, Input switch, Overcurrent protection, Temperature protection |
| Protection | Hardware Protections | Breaker for input,Output,Battery and bypass. Fast acting fuses in DC,Fans,Redundant power supplies,Temperature,Temperature sensors,On-0 switch and audible alarms. |
| Bypass | Static solid state,Automatic and manual operation without interruption for maintenance.External bypass(optional) |
| Emergency Switch | Remote and / or local EPO |
| Supervisory Control and Communication | Frontal Panel | Interactive LCD Display(Touchscreen) |
| Alarms | Audivle and visual alarm for abnormal conditions |
| Communications | RS232,SNMP-RJ45,GPRS module for network remote monitoring |
| UPS(L*W*D) | 540*1120*620 | 660*1550*860 | 660*1550*860 | 800*1800*1120 |
| Battery Case(L*W*D) | 270*1125*774 | 432*1550*897 | 432*1550*897 | 650*1800*1004 |
| UPS Weight(KG) | 225 | 437 | 600 | 780 |
| Battery Case Weight(KG) | 59 | 105 | 105 | 142 |
| Temperature | 0℃ ~ 40℃ |
| Relative Humidity | 0 ~ 95%, Non condensing |
| Noise | <60db at 1.5m from surface of unit |
| Altitude | 1000m (height rises every 100m, power decreases 1%, maximum height is 4000m) |
| Efficiency | >92% |
| *Product Specifications are Subject to Change Without Notice. |