| Model | JS11 6K | JS11 10K | JS11 15K | JS11 20K |
| Capacity (KVA) | 6KVA | 10KVA | 15KVA | 20KVA |
| Power ( Watts ) | 4.8KW | 8KW | 12KW | 16KW |
| Grid (AC Input) | |
| Max input current (A) | 37 | 61 | 91 | 121 |
| Type | Single Phase ( P+N+PE ), 220VAC |
| Input voltage | 50/60Hz±5% |
| Input frequency | 220/230/240VAC±25% (100/110/120VAC is optional) |
| Charge voltage | 219V±1% |
| Charge current | 0-3A-6A, Can adjust through panel switch |
| PV | |
| PV1 | 300VDC --- 400VDC (2 groups max) |
| PV2 | 300VDC --- 400VDC |
| Charge current | 20A max (PV1) |
| Battery | |
| Type | Maintenance free lead-acid battery (other type battery need customize ) |
| Battery voltage | 192VDC |
| Battery capacity | According to backup time |
| Battery low voltage protection | >172.8V |
| Inverter (Output) | |
| Inverter output waveform | Pure sine wave, THD<3% (linear load) |
| Inverter voltage | 220/230/240VAC±1%(stable load), 220/230/240VAC±5% (load fluctuation), |
| (100/110/120VAC is optional) |
| Frequency | 50/60Hz±0.5% |
| Dynamic feature | Inverter output transient dynamic range less than±5%,recovery time <20mS |
| Crest factor | 3:01 |
| Overload protection | (Inverter output)125% overload, delay 1mins protect, 150% overload, immediate protect |
| Inverter efficiency | >90% ( 99% load ) |
| System Parameters | |
| Transfer time | <0.5ms ( inverter--bypass ) |
| Protection | Output short circuit, overload, overvoltage, under voltage, |
| over temperature etc protection, have audible and visual alarm |
| Display | LCD display input and output voltage, output current, the inverter voltage, frequency, output current, battery voltage, PV voltage, PV charging current, temperature mode, flowcharts, current work status, event record and system information |
| Operating environment | Temperature 0-40℃ |
| Relative humidity | 30%-95% |
| Work sequence | Solar-Grid-Battery or Solar –battery-Grid, Can choose one of the mode via LCD panel |
| Operation altitude (max) | <1000 meters ( per increase 100 meters power decrease 1%, at most 4000 meters ) |
| Computer communicate | RS232/RS485 |
| interface |
| Cooling method | force-air cooling |
| Size W*D*H (mm) | 300*570*850 | 350*600*850 |
| Weight (kg) | 108 | 146 | 162 | 178 |
| *Product specification are subject to change without further notice. |