Structure:
Frame | Filter Media | Gasket |
Aluminum/Galvanised steel/plastic | Multi-layer synthetic fiber combined with Activated carbon granules | Aluminum/Galvanised steel/plastic |
Features
-Strong Absorption capacity for the air dust, odour and other organic pollutants
-Widely used in various ventilation systems
Application: As prefilters for air conditioning systems, such as commercial buildings, hospitals, airports, etc. It can absorb odorous substances such as benzene, formaldehyde, ammonia and CO2.
Technical Data:-G4~F8 EN799; MERV6~15 (ASHRAE 52.2-2012)
-Max air flow rate: 125% of nominal air flow rate
-Final pressure drop: (recommend) 400~450Pa (M6-F8)
-Thermal Stability: 60%
-Humidity: 70%
Sample data:
W*H*D(mm) | Filter Class | Dust Spot Efficiency | Benzene Absorption | Filter Area(m²) | Airflow(CMH) | Intial Pressure Drop(Pa) |
592*592*535 | M6 | 60%-80% | ≥220mg/g | 6.20 | 3400 | 120 |
287*592*535 | M6 | 60%-80% | ≥220mg/g | 3.10 | 1700 | 120 |
592*592*535 | F7 | 80%-90% | ≥200mg/g | 6.20 | 3400 | 140 |
287*592*535 | F7 | 80%-90% | ≥200mg/g | 3.10 | 1700 | 140 |
592*592*535 | F8 | 90%-95% | ≥180mg/g | 6.20 | 3400 | 160 |
287*592*535 | F8 | 90%-95% | ≥180mg/g | 3.10 | 1700 | 160 |