Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum, insulated with either polyethylene or XLP crosslinked polyethylene.
Neutral messengers are concentrically stranded 6201, AAC, or ACSR, One conductor is manufactured with an extruded ridge for phase identification.
Standards
ASTM B-230, B-231, B-232, B-339 & ICEA S-76 -474
Code Name | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft(lbs) | Rating(Amps) |
Size AWG | Strand | Insulation thickness (mls) | Size AWG | Strand | Breaking strength (lbs) | XLP | POLY | XLP | POLY |
AAC NEUTRAL-MESSNGER |
Clydesdale | 4 | Solid | 45 | 4 | 7 | 881 | 208 | 201.8 | 100 | 80 |
Pinto | 4 | 7/w | 45 | 4 | 7 | 881 | 223 | 207.9 | 100 | 80 |
Mustang | 2 | 7/w | 45 | 2 | 7 | 1,350 | 333 | 312.6 | 135 | 105 |
Criollo | 1/0 | 19/w | 60 | 1/0 | 7 | 1,990 | 529 | 504.5 | 180 | 140 |
Percheron | 2/0 | 19/w | 60 | 2/0 | 7 | 2,510 | 649 | 620.5 | 205 | 160 |
Hanoverian | 3/0 | 19/w | 60 | 3/0 | 19 | 3,310 | 799 | 765.6 | 235 | 185 |
Oldenburg | 4/0 | 19/w | 60 | 4/0 | 19 | 4,020 | 986 | 946.7 | 275 | 210 |
Lippizaner | 336.4 | 19/w | 80 | 336.4 | 19 | 6,146 | 1,546 | 1,519.2 | 370 | 280 |
ACSR NEUTRAL-MESSNGER |
Morochuca | 6 | Solid | 45 | 6 | 6/1 | 1,190 | 152 | 147.4 | 75 | 60 |
Chola | 6 | 7/w | 45 | 6 | 6/1 | 1,190 | 162 | 151.7 | 75 | 60 |
Morgan | 4 | Solid | 45 | 4 | 6/1 | 1,860 | 226 | 220 | 100 | 80 |
Hackney | 4 | 7/w | 45 | 4 | 6/1 | 1,860 | 241 | 226.1 | 100 | 80 |
Palomino | 2 | 7/w | 45 | 2 | 6/1 | 2,850 | 362 | 342.6 | 135 | 105 |
Costena | 1/0 | 19/w | 60 | 1/0 | 6/1 | 4,380 | 575 | 550.6 | 180 | 140 |
Grullo | 2/0 | 19/w | 60 | 2/0 | 6/1 | 5,310 | 707 | 678.7 | 205 | 160 |
Suffolk | 3/0 | 19/w | 60 | 3/0 | 6/1 | 6,620 | 872 | 838.9 | 235 | 185 |
Appaloosa | 4/0 | 19/w | 60 | 4/0 | 6/1 | 8,350 | 1079 | 1039.2 | 275 | 210 |
Bronco | 336.4 | 19/w | 80 | 336.4 | 18/1 | 8,580 | 1613 | 1568.2 | 370 | 280 |
Gelding | 336.4 | 19/w | 80 | 4/0 | 6/1 | 8,350 | 1548 | 1494.3 | 370 | 280 |
|
Code Name | Phase Conductor | Bare Neutral Messenger | Weight Per 1000 ft(lbs) | Rating(Amps) |
Size AWG | Strand | Insulation thickness (mls) | Size AWG | Strand | Breaking strength (lbs) | XLP | POLY | XLP | POLY |
6201 ALLOY NEUTRAL-MESSENGER |
Bay | 6 | Solid | 45 | 6 | 7 | 1,110 | 145 | 140.0 | 75 | 60 |
French Coach | 6 | 7/w | 45 | 6 | 7 | 1,110 | 155 | 144.3 | 75 | 60 |
German Coach | 4 | Solid | 45 | 4 | 7 | 1,760 | 214 | 208.3 | 100 | 80 |
Arabian | 4 | 7/w | 45 | 4 | 7 | 1,760 | 229 | 214.4 | 100 | 80 |
Belgian | 2 | 7/w | 45 | 2 | 7 | 2,800 | 344 | 323.1 | 135 | 105 |
Shetland | 1/0 | 19/w | 60 | 1/0 | 7 | 4,460 | 546 | 521.1 | 180 | 140 |
Thoroughbred | 2/0 | 19/w | 60 | 2/0 | 7 | 5,390 | 670 | 641.5 | 205 | 160 |
Trotter | 3/0 | 19/w | 60 | 3/0 | 7 | 6,790 | 825 | 791.8 | 235 | 185 |
Walking | 4/0 | 19/w | 60 | 4/0 | 7 | 8,560 | 1019 | 979.7 | 275 | 210 |