How to choose the capacity of the soft starter?
Load capacity of soft starter
The load capacity of the soft starter mainly refers to the overload capacity. Due to the difference of the actual working system, the actual loading situation of the soft starter is also different. For example, during the starting process, it will generally bear 2-4 times the rated current, and the time is usually within 60S. Therefore, for the long-term working system, the soft starter actually belongs to the short-time overload work during the starting process; and for the repeated short In terms of the hourly duty system, the soft starter actually belongs to long-time overload work during the starting process. Since the heat capacity of power semiconductor devices (thyristors) is very small, the overload capacity of the device is mainly determined by the overload capacity of the power conductor device and the heat dissipation capacity of the soft starter.
The overload capacity of the soft starter is generally designed according to the following principles:
1. The overload that lasts for more than 15 minutes is generally designed according to the continuous load condition.
2. For overloads that last less than 15 minutes, calculate the device's overload capacity and select the device by calculating the junction temperature of the device according to the transient thermal impedance curve of the thyristor device.
Therefore, when choosing a soft starter, you should refer to its related instructions to clarify the applicable rated work system and applicable standards of the product to determine the actual load capacity of the product.
Note: Generally speaking, the larger the thyristor capacity, the larger the size of the radiator, and the larger the cooling fan, the stronger the load capacity of the corresponding soft starter. Of course, the volume and cost of the corresponding equipment are higher. For power electronic equipment, under the same capacity, it is by no means that the smaller the size, the better. This point should be paid attention to.
Capacity selection of soft starter
In principle, the choice of soft starter capacity should be greater than the capacity of the motor to be driven.
The rated capacity of the soft starter usually has two kinds of nominals, one is nominal according to the corresponding motor power, and the other is nominal according to the maximum allowable working current of the soft starter.
The following two points should be noted:
1. According to the nominal power of the driven motor, products of different voltage levels have different rated currents. For example, for a 75KW soft starter, if its voltage level is AC380V, its rated current is 150A, and if its voltage level is AC660V, its rated current is 100A.
2. According to the maximum allowable working current of the soft starter, the rated capacity of products with different voltage levels is different. For example, for a 160A soft starter, if the voltage level is AC380V, the rated capacity is 75KVA; if the voltage level is AC660V, the rated capacity is 132kva.
The selection of soft start capacity should also be considered comprehensively, such as the soft starter's load capacity, working system, environmental conditions, cooling conditions, etc.
The corresponding relationship between rated current and controlled motor power is recommended to be selected according to the table below.
What needs to be explained here is: As a general principle, the motor full-voltage locked-rotor torque is more than the load starting torque, the easier it is to control the starting process; but simply increase the capacity of the soft starter without increasing the motor The capacity cannot increase the starting torque of the motor.
When the capacity must be increased
There are mainly the following situations in which the capacity of the soft starter must be increased:
1. The soft starter running on-line full pressure or the soft starter using the energy-saving control method is often running under heavy load. Since the rated current of the soft starter is compared with the motor of the same grade, the current margin is relatively small. Therefore, if the motor often runs under heavy load conditions, its operating current can easily exceed the rated current of the soft starter, which may cause the soft starter to overload during operation, so the capacity of the soft starter should be appropriately increased.
2. The motor is used for continuously variable load or intermittent load, and the cycle is short. In this case, the motor is not allowed to run under short-term overload. Otherwise, the soft starter may be overloaded during operation, so the soft starter The capacity should be increased appropriately.
3. The motor is used for repeated short-time work, and the period is less than the start time interval specified by the manufacturer, which may cause soft start overload during the start, so the capacity of the soft starter should be appropriately increased.
4. Some loads are too heavy or the grid capacity is too small. When starting, the starting time of the motor is too long, causing the soft starter to overload and trip. On the premise that the motor is not damaged, the capacity of the soft starter can be appropriately enlarged.
5. For loads with special requirements for acceleration time, the length of the motor acceleration time is a relative concept related to the inertia. Some loads require a short acceleration time, and the acceleration current of the motor will be relatively large. At this time, the capacity of the soft starter can be appropriately enlarged to solve the problem.
6. There is a load with large inrush current during the transition process, which may cause the overcurrent protection to operate. At this time, the capacity of the soft starter can be appropriately enlarged to solve the problem.
The SAFESAVE-SJR3 series of soft starters have gone through dozens of iterations for ten years since the beginning of research and development. The technology has already been very mature, and the cost performance and functions are very suitable for today's small and medium-sized enterprises. We sincerely hope to get inquiries from new and old customers.