MS series aluminum housing 1hp 3 phase motor is made of superior materials and conform to the IEC standard. MS motors have good performance, low noise, safety, reliable operation and nice appearance. It can be maintained very conveniently. This motor 1hp 3 phase has advantages of little vibration, light weight and simple construction. These 1 hp motor 3 phase can be used for general drive such as water pumps, water treatment, road machinery, petroleum, chemical, metallurgy, cement and paper industries.
Product Detail
Motor Type: 3 phase 1hp motor
Output Power: 0.06 kW - 18.5 kW
Frame Size: IEC Frame 56 - 160
Number of Poles: 2 / 4 / 6 / 8
Voltage: 220/380V, 380/660V, 230/400V, 400/690V
Frequency: 50 & 60 Hz
Protection Level: IP54 / IP55
Energy Efficiency Rating: IE1 / IE2 / IE3
Insulation Class: B/F
Cooling Method: IC411
Working System: S1
Product Parameter (Specification)
Motor 1 hp 3 phase
Type | Power HP | Rated Current (A) | Speed (r/min) | Eff (%) | Power Factor CosØ | Rated Torque Tn(N*m) | Tst/Tn | Tmax/Tn | Ist/In | |||||
220V | 380V | 660V | 230V | 400V | 690V | |||||||||
3000rpm.2 poles | ||||||||||||||
MS2-801-2 | 1 | 3.1 | 1.79 | 1.03 | 2.95 | 1.71 | 0.98 | 2840 | 77.4 | 0.82 | 2.52 | 2.3 | 2.3 | 6.8 |
1500rpm.4 poles | ||||||||||||||
MS2-802-4 | 1 | 3.25 | 1.88 | 1.08 | 3.1 | 1.79 | 1.03 | 1410 | 79.6 | 0.76 | 5.08 | 2.3 | 2.3 | 6.4 |
1000rpm. 6 poles | ||||||||||||||
MS2-90S-6 | 1 | 3.65 | 2.11 | 1.22 | 3.48 | 2.01 | 1.16 | 925 | 75.9 | 0.71 | 7.74 | 2 | 2.1 | 5.8 |
Production Features
Know More Us
Why Us
Service and Packing
About motor
Inspection method of three-phase wound high-voltage asynchronous motor
1.1 Stator
(1) The insulation value of the stator of the high-voltage motor to the ground is not less than im. /Such as a 6kV high-voltage motor, the stator-to-ground insulation value is not less than 6m, and the electrician uses a 2v high-voltage shaker to measure it every half month and record the change. If the resistance value of the motor changes greatly or the measured value is less than 6Mo, the motor should be thoroughly inspected or replaced.
(2) The electrician uses the double bridge to measure the DC resistance between the stator phases of the high-voltage motor every month, and record the resistance value. The unbalance of the three-phase resistance does not exceed 5%. If this value is exceeded, it indicates that there may be a problem with the motor branch coil and should be thoroughly inspected or planned to be replaced.
1.2 Rotor
(L) The position or electrician should check the motor slip ring, carbon brush and compression spring every day. The slip ring has no sparks, the length of the carbon brush is not less than 1/3 of the total length, and the compression spring ring is not damaged
(2) Electricians use Zhounov low-voltage shaker to test the motor rotor once every half month. The insulation value of the rotor to the ground is not less than 1mq/kV. If it is lower than this value, the motor should be thoroughly inspected or replaced in a planned way. )
1.3 Bearing
(1) When cleaning the bearing housing of the working bearing motor, check the temperature once. The normal working temperature is ling-4()℃, 4()-5()℃ is abnormal. If the temperature reaches 4~-5~, the electrician should check. The maximum temperature should not exceed 6 () ℃. If the temperature exceeds 4()-5()℃, the motor should be replaced. In addition, the oil in the base should be changed at least once every three months.