Welcome Customer !

Membership

Xuzhou Sanhe Automatic Control Equipment Co., Ltd.
Free Member ·1YRS
,
Other

Main Products: 数字温度计

Xwboo>Products
Product Categories

Xuzhou Sanhe Automatic Control Equipment Co., Ltd.Free·1YRS

  • E-mail

    arisa@jindian2008.com

  • Phone

  • Address

    No. 18, Minyuan Road, Tongshan New District, Xuzhou City, Jiangsu Province

Contact Now

High-quality refrigeration and heating conversion thermostat STC-9200 for industrial use

Model
Nature of the Manufacturer
Other
Product Category
Place of Origin
City, Province
Overview
Short Description: Multi-control mode among refrigeration,defrost and fan;User menu and administrator menu can be set separately.Not only converient for user operation,but also left enough space for the adjustment of high-level management;Differential control mode,and the resolution of temperature display is 0.1;Multi-protection and alarm mode optional;CORYKEY function(optional). Service offered: Customized LOGO, labeling, customized packaging boxes, customized products, etc. acco......
Product Details

Our company specializes in R&D, production and sales of microcomputer temperature controllers and humidity controllers. The chip used in the temperature controller has stable performance, complete functions, multiple protections, advanced and reasonable structural design and process processing, and the technical level is internationally advanced and domestically leading . This product has a wide range of applications in the field and industry of freezing and refrigeration and refrigeration maintenance. Our company can also design and customize products according to customer requirements.

Features and functions

Multi-control mode among refrigeration,defrost and fan;
User menu and administrator menu can be set separately.Not only converient for user operation,but also left enough space for the adjustment of high-level management;
Differential control mode,and the resolution of temperature display is 0.1;
Multi-protection and alarm mode optional;
CORYKEY function(optional).
Specification:
Product size:75*34.5*85mm
Installation size:71*29mm
Technical parameters:
Temperature measuring range:-50℃~50℃
Power supply:220VAC,50Hz
Power consumption:<5W
Ambient temperature:0℃~60℃
Relative humidity:20%-85%(No condensate)
Accuracy:±1℃
Relay capacity of compressor:8A/220VAC
Relay capacity of alarm and defrost:8A/220VAC
Digital display:Three-digit LED+Minus digit+Status indicator light

Specification

Product size:75*34.5*85mm
Installation size:71*29mm

Technical parameters

Temperature measuring range:-50℃~50℃
Power supply:220VAC,50Hz
Power consumption:<>
Ambient temperature:0℃~60℃
Relative humidity:20%-85%(No condensate)
Accuracy:±1℃
Relay capacity of compressor:8A/220VAC
Relay capacity of alarm and defrost:8A/220VAC
Digital display:Three-digit LED+Minus digit+Status indicator light

Descriptions off Indicator Light

Indicator LightStatusMeaning
Refrigeration Indicator LightLight offCompressor stops
Light flashesCompressor delays
Light onCompressor works
Light flashes quicklyForcible refrigeration
Defrost Indicator LightLight offDefrost stops
Light flashesDefrost dripping
Light onDefrost works
Light flashes quicklyForcible defrost
Fan Indicator LightLight offFan stops
Light flashesFan delays
Light onFan works
Set Indicator LightLight offNormal working status
Light onUnder setting status

Function description

Compressor
under electric-heating defrost status, and fan delay set time>Os:
Activation condition: Relay of the compressor connects when it meets both a)> b) or both a)、c).
Compressor delay time exceeds the set delay time.
The storage temperature is higher than the set temperature, and the forcible refrigeration starts,
Under non-defrost status, the storage temperature is higher than the set temperature+ differential set value.
(When fan delay time vOs, if it meets the activation conditions and compressor runs out of delay absolute value, relay of compressor connects.)
Stop condition: Relay of compressor disconnects when it meets any of the ff. conditions.
Storage temperature is lower than the set temperature.
At start-up of defrost.
Forcible refrigeration stops.
under thermal defrost status:
Activation condition: Relay of the compressor connects when it meets both a)、 b),a)、 c)or a)、 d).
Compressor delay time exceeds the set delay time.
Under non-defrost status , the storage temperature is higher than the set temperature+ differential set value.
The storage temperature is higher than the set temperature, and forcible refrigeration starts.
When defrost
(When fan delay time<0sf if="" it="" meets="" the="" activation="" conditions="" and="" compressor="" runs="" out="" of="" delay="" absolute="" value,="" relay="" of="" compressor="">

STC-9200 (1) STC-9200 (2) STC-9200 (3) STC-9200 (4) STC-9200 (5) STC-9200 (6) STC-9200 (7) STC-9200 (8) STC-9200 (9) STC-9200 (10) STC-9200 (11) STC-9200 (12)