Introduction of horizontal boiler
Automatic boiler including horizontal, three-pass, wet back shell boiler. The main structure includes: Boiler shell, Bellows furnace, Returns burns room, Threaded gas pipe, etc. The shell and the furnace are made by 20g boiler special steel. Furnace & Returns burns room, Tube plate & Boiler shell and Returns burns room & Returns burns room cylinders are connected by the method of the flanged edge connecting.
Advantages of horizontal boiler
There is more heating surface to spare in order to assure of running of full load and overcharge.
Proportional control: with procedure ignition, automatically blowing and flameout protective device. And it has many merits such as good burning effect, the reliability of ignition, burning rapidly, mix evenly with air and gas and adjusting the scale of fuel gas and air. The burning efficiency is over 99.5%.
The furnace shape is fit for the shape of a flame, avoiding the flame washing out the heating surface area.
Flue gas consistency is low with less pollution.
Heating efficiency is high.
The furnace adopts the wet back structure, with the merits of good diathermanous effect and less heat loss. The temperature of rear flue chamber is low so that the operators feel comfortable and safe.
Boiler adopts light quality thermal insulation material: Aluminum Silicate Fibre, with the merits of light quality, good heat preservation, less heat lost, high heating efficiency, etc.
The automatic control degree of the boiler is high, adopting programmable computer control. The control box adopts full automatic operating to actualize Auto-igniting and Auto-boiler outage. And it also has a manual switch.
The boiler-burning device adopts Auto scale adjusting method. Outlet water temperature is automaticlly adjusted.
The automatic control protection procedure has full functions, such as automatically blowing, fuel gas leak alarm, safe operating chain protecting, flameout protecting, fuel gas pressure protecting, etc.
Inspecting and adjusting function is full, such as automatically blowing, fuel gas leak alarm, safe operating chain protecting, flameout protecting, fuel gas pressure protecting, boiler over pressure voice-and-light alarm and boiler feed water over temperature voice-and-light alarm, etc.
Boiler also has the burner motor overload protecting device and Auto- engine off protecting the device. The boiler equips the Max pressure limit device, fuel gas Min pressure limit device and Max temperature limit device.
Boiler set the explosion-proof gate to keep safe.
Boiler control system, alarm system, and safe protecting system are relatively independent setting and configuring. The pressure changes delivering and the temperature changes delivering can make the burner automatic off when temperature or pressure is overload.
Working principle of horizontal boiler
Steam boiler stove for single drum longitudinal water tube boiler shell boiler. Grate combustion equipment for activities. Left and right sides of the chamber of a stove water wall as the radiation heating surface, the two wings of the flue and threaded pipe inside the drum for convection heating surface. Furnace wall and two side wall outside before and after using the brick masonry.
Technical data
Item | DZL2-1.25-ALL | DZL4-1.25-ALL | DZL6-1.25-ALL |
Rated Evaporation (T/H) | 2 | 4 | 6 |
Rated Working Pressure (Mpa) | 1.25 | 1.25 | 1.25 |
Saturated Steam Temperature(℃) | 193 | 193 | 193 |
Boiler Thermal Efficiency (%) | 76 | 76 | 81 |
Grate Area (m²) | 4.2 | 4.97 | 8.22 |
Design Types of Coal | II Types Soft Coal | II Types Soft Coal | II Types Soft Coal |
Heating Area (reference) (m²) | 86.2 | 145.92 | 236.57 |
Reference Weight (t) | 24.147 | 26.518 | 37.492 |
Size(L*W*H) (m) | 5.65*2.6*3.23 | 6.847*2.7*3.17 | 6.886*2.87*3.68 |
Name | DZL2-1.25-ALL | DZL4-1.25-ALL | DZL6-1.25-ALL |
Blowers | Model: 4-72-11 No.3.6A Spindle speed: 2900 r/min Entire pressure: 1578-989Pa Flow: 2664-5268m³/h Motor: Y100L1-2 ; 3kw | Model: 4-72-11 No.4A Spindle speed: 2900 r/min Entire pressure: 2014-1320Pa Flow: 4012-7419m³/h Motor: Y100LS1-2 ; 5.5kw | Model: 4-72-11 No.4.5A Spindle speed: 2900 r/min Entire pressure: 1660Pa Flow: 10580m³/h Motor: Y100LS1-2 ; 7.5kw |
Induced draft fan | Model: GY2-18 No9.8D right 90 Spindle speed: 1450 r/min Entire pressure: 4037-3959 Pa Flow: 5000-9021 m³/h Motor: Y160L-483; 15kw | Model: Y5-47 No6C Spindle speed: 2800 r/min Entire pressure: 3364-2452 Pa Flow: 8020-15129 m³/h Motor: Y160L-2; 18.5kw | Model: Y6-41 No9C Spindle speed: 1750 r/min Entire pressure: 3338-2495 Pa Flow: 25630 m³/h Motor: Y200L-4B; 30kw |
Water pumps | Model: 1½ GC-5x7 Flow: 6m³/h Pumphead: 165m Rotating speed: 2900r/min Motor: Y135S2-2; 7.5kw | Model: 1½ GC-5x7 Flow: 6m³/h Pumphead: 161m Rotating speed: 2950r/min Motor: Y135S2-2; 7.5kw | Model: 1½ JGGCB-176x22 Flow: 7.5m³/h Pumphead: 168m Rotating speed: 2900r/min Motor: Y135S2-2B5; 7.5kw |
Grate velometer | Model: XBL22A Torque: 5000Nm Motor: Ys7124; 0.37kw | Model: XBL22A Torque: 5000Nm Motor: Ys7124; 0.37kw | Model: WTG6 Torque: 7000Nm Motor: 0.37kw Electromagnetic speed-adjustable motor |
Mucking machine | Model: GBL-03 Slag volume: 300kg Spindle speed: 7.02r/min Motor: Y90L-6; 1.1kw | Model: GBL-03 Slag volume: 300kg Spindle speed: 7.02r/min Motor: Y90L-6; 1.1kw | Model: LX Slag volume: 1500kg Spindle speed: 4.87r/min Motor: Y90L-4B5 |
Coal conveyor | Model: FSG Coal scuttle capacity: 100kg Motor: Y90S-4; 1.1kw | Model: FSG Coal scuttle capacity: 135kg Motor: Y90S-4; 1.1kw | Model: XGS Coal scuttle capacity: 150kg Motor: Y90S-4; 1.1kw |
Dust remover | Model: CCD-III | Model: CCD-III | Model: DX6 |
Electrical control cabinets | Model: CKC-II | Model: CKC-IV | Model: CKC-6L |