PVgrid-connected power generation system consists of PV modules, grid-connectedinverters, metering devices and power distribution systems. The PV moduleconverts solar energy into DC power. The DC power is converted into ACsinusoidal energy of the same frequency and in phase with the grid through thegrid-connected inverter. The DC power is supplied to the local load and therest to the grid.
● Use the United States TIDSP chip control
● High conversion efficiency
● Advanced Maximum PowerPoint Tracking (MPPT)
● MPPT efficiency> 99%
● Wide voltage input range
● Disturbance detectiontechnology to achieve anti-islanding control
● Perfect protectionfunction, the system reliability is higher
● pure sine wave output,automatic synchronization and network, the current harmonic content of small,non-polluting power grid, no impact
● equipped with RS485 /RS232, Ethernet, GPRS (optional) interface, remote data acquisition andmonitoring.
Type | BNSG10KS | BNSG30KS | BNSG50KS | BNSG100KS |
Isolation | Low frequency transformer isolation |
Max. DC input power | 11KWp | 33 KWp | 55 KWp | 110 KWp |
Max. DC input voltage | 900Vdc |
Max.PV voltagerange(MPPT) @best operating point | 400Vdc~820Vdc @595Vdc | 450Vdc~820Vdc @595Vdc |
Recommended number of PV module voltage@string | About35V@17string |
Battery board Joint type | connection terminal |
Max. Input current | 27.5A | 73.3A | 122A | 245A |
Nominal AC output power | 10KW | 30 KW | 50 KW | 100 KW |
Max. AC output power | 11KW | 33 KW | 55 KW | 110 KW |
THD of AC current | <3%(nominal power) |
Power factor | >0.99 |
Max. Efficiency | 95% | 96% | 96.5% |
Euro efficiency | 93% | 94% | 95.2% |
Permitted voltage range | 310Vac~450Vac(adjustable) |
Permitted frequency range | 58.5Hz~61.5Hz |
Internal power consumption an night | <100W |
Automatically put into operation conditions | When the DC input and power grids meet to the requirements, the inverters automated operation |
Automatic restart time | 5min(time adjustable) |
Protection | Possess the protecting function of polarity connecting contrary, short circuit, island effects, over heat,over land |
Comm. interfaces | RS485/RS232/GPRS/Ethernet |
Operating Temp. | -20°C~+55°C |
Relative humidity | 0~95%,no condensing |
Altitude(m) | ≤2000meters(Over 2000 meters to reduce the using amount) |
Cooling method | Controlled forced-air cool |
Noise | ≤60dB |
Protection degree | IP20(indoor) |
Size(W*L*H mm) | 580*515*1250 | 800*600*2060 | 800*600*2060 | 1000*800*2060 |
Weight(kg) | 150 | 400 | 700 | 900 |