Performance Parameters
| Integrated with RSS485 extension communication function description |
| RS485 communication | Communication port | 2 communication port: |
| PORT0:PPI/Free port,standard RS485 |
| PORT1:PPI/Free port,standard RS485 |
After plugging in the RS485 expansion board and restarting PORT0:RS485,PPI port PORT1:RS485,PPI/Free port FPORT0:Free port |
| PPI baud rate(baud) | 9.6k、19.2k and187.5k |
| Free port baud rate(baud) | 1.2k ~ 115.2k |
| Use isolation repeater | Baud rate is 1000 m at 187.5 and 1200 m at 38.4 K |
| No isolation repeater | 50m |
| Maximum number of stations | Maximum number of stations is 32 for each segment and 126 for each network |
| Maximum number of master stations | 32 |
| Point-to-point (PPI master mode) | Yes (NETR/NETW), with a maximum of 8 connections, each connection communicating a maximum of 200 bytes |
| MPI connections | 8 MPI connections (1PG/1OP), with 2 reserved |
| Isolation | None |
Note: After using the RS485 expansion board, the PLC communication port changes as follows:
Original communication port:
Port 0: PPI/ Free port, standard RS485
PORT1: PPI/ Free port, standard RS485
After plugging in the RS485 expansion board and restarting, the communication port changes as follows:
PORT0 (RS485, PPI port)
PORT1 (RS485, PPI/ Free port), Fport0 (free port)