Physical Features |
Dimension(W×H×D) | 137×80×62mm |
Power dissipation | 7W |
Memory Features |
Program memory | 24KB,can be expand to 72KB |
Data memory | 10KB,can be expand to 110KB |
Power-off protection time(super capacitor ) | 112 hours(typical) |
External battery (Optional) | 200 days(typical) |
General Features |
| Counters total | 256(super capacitor backup) |
Internal memory bits | 256(super capacitor backup) |
Stored permanently on power down | 112 hours(typical) |
Time Interrupts | 2 with 1ms resolution |
Edge Interrupts | 4 rising edges and/ or 4 falling edges |
Analog adjustment | 2 with 8 resolution |
Boolean execution speed | 0.15µs |
Float execution speed | 8µs |
Clock | Embedded |
Rated voltage | 220VAC |
Power supply Native and extended bus+5V +5V +24V | 1A 10mA 300mA |
Integrated Communication Function |
Communication port | 2 communication ports ,PORT0:PPI/Free port,RS485;FPORT1:PPI/freeport, RS485 PWL |
PPI baud rates(baud) | 9.6k、19.2k and187.5k |
Freeport baud rates (baud) | 1.2k ~ 115.2k |
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied | When it is 1000 m, baud rate is 187.5k; when it is 1200 m, 38.4k. 50 m |
Maximum number of stations | 32 stations per segment,126 stations per network |
Maximum number of masters | 32 |
Point to point (PPI Master Mode) | Yes(NWTR/NETW), 8 total, 2 reserved |
Ethernet Function |
Communication port | 1 Ethernet port |
Communication standard | IEEE802.3 standard |
Communication speed | 10Mbps and 100Mbps self-adaption |
Adaptive cross connection | Non support |
Interface to industrial Ethernet(10/100Mbps) | RJ45 |
Protocol type | UDP/TCP protocol Support MICO Ethernet programming, support Ethernet communication between PLC. |
Collocation method | Support the upper computer through the Ethernet port search PLC, support the mouth download system configuration. |
Max Connections | Each PLC supports up to 8 UDP connections and up to 4 TCP connections. |
The maximum number of IT connections | 8 UDP_PPI connections, with 4 master stations and 4 slave stations.
4 ModBus_TCP connections, 2 master stations and 2 slave stations. |
User data number | Up to 200 bytes are used for TCP/IP transmission. Up to 240 bytes are used for ModBus_TCP transport. |
Port | local:1~65535 remote server:8888 |
Boot time or restart time after reset | 3 seconds |
Indicator lamp | Green RMC indicator: on: remote control in effect, off: remote control out
Green Ethernet indicator: on: connection, flicker: transmission; out: not connected |
Maximum cable length | 100m |
Isolation | Communication port |
I/O Feature |
Number of integrated digital inputs | 14 |
Input type | Sink/Source |
Number of integrated digital outputs | 10 |
Output type | Relay dry contact |
Digital I/O mapping domain | 640DI/640DQ |
Analog I/O mapping domain | 194AI/194AQ |
Maximum number of expandable I/O modules | 7 |
Pulse catch inputs | 14 |
High-speed counters Total Uniphase counters Bi-phase counters | 6 6×30KHz 4×20KHz |
Digital Input Features |
Number of integrated digital input | 14 |
Input type | Sink/ Source |
Rated voltage | 24V DC |
Input voltage range | 20.4~28.8V DC |
Surge voltage | 35V DC,continuously 0.5s |
Logical 1 Signal (minimum) Logical 0 Signal (Maximum ) | 15 VDC,2.5mA 5 VDC,1mA |
Connect 2 wire proximity switch sensor (BERO) Allowable leakage current (maximum) | 1mA |
Input filter | support 0.2ms,0.4ms,0.8ms,1.6ms,3.2ms,6.4ms,12.8ms,default 6.4ms |
Isolation(field side to logical circuit) Isolation groups | 500V AC,1min refer to wiring diagram |
Simultaneous input | 14 |
Maximum cable length Shielded Unshielded | 500 M(standard input) 50 M(high-speed counters input) 300 M(standard input) |
Digital Output Features |
Number of integrated digital output | 10 |
Output type | Relay dry contact |
Rated voltage | DC:24V,AC:110V/220V |
Output voltage range | DC:5~30V,AC:5~250V |
Output current (Max) | 2A |
Surge current | 5A,4s@10% duty ratio |
Lamp load | DC:30W /AC:200W |
On resistance | Max 0.2Ω |
Input delay | Max 10ms |
Switching frequency(Max) | Resistive load :10Hz Lamp load:1Hz Inductive load:0.5Hz |
Mechanical life cycle | 10,000,000 |
Contact endurance | 100,000 |
Simultaneous output | 10 |
Parallel output | Only when the outputs are in the same group |
Maximum cable length Shielded Unshielded | 500m 150m
|