Terminal Connection
Weighing module which is a measuring module of high-precision requires reliable measuring low signal level (about 1.5uV). Thus, to make sure it works, it is important to choose appropriate
assembly and cable connection.
While connect weighing transducer, following rules should be obeyed.
· If more than one transducer is going to be connected (if they are weighing transducers,
they must be parallel connected), one junction box must be used. If the distance between
weighing transducer and module or between weighing transducer and junction box is
longer than the length of available cable of weighing transducer, a dedicated extension box
Should be used.
· Shield of cable should always reach as far as to cable gland of junction box or extension box.
· Use stranded wire to connect cable in certain circuit and keep it shielded.
---transducer wire SEN+/SEN-;
---measuring voltage coil SIG+/SIG-;
---supply voltage coil EXC+/EXC-.
·Shielded wire must be joint with shield connector.
Four- Wire connection
When connect four-wire transducer, please make sure that EXC with SENS, EXC with SENS- are short
circuited. Otherwise, the module may not work normally.
2、Six-wire connection

3、Module Connection Diagram

DIP Switch Setting
DIP Switch Configuration |
Switch 1、2、3、4、5、6 | setting | function |
SW1、2 | 01 | Choose 1mV/V transducer |
| 00 | Choose 2mV/V transducer (default) |
| 10 | Choose 3mV/V transducer |
| 11 | Choose 4mV/V transducer |
SW3 | 0 | Choose dual channel working model (default) |
| 1 | Choose uni-channel working model |
SW4 | 0 | Choose filter1(default) |
| 1 | Choose filter 2 |
SW5、6、7、8 | 00 | Spare, reserved |
Remark: Ø Default state:000000 Ø Which filter to be used is determined by software according to need of debug. |