Wentang Road,Chashang industrial zone #18,Dongcheng,Dongguan,Guangdong,China
Description
< ±0.5% Regulation
Suitable for brushless type generator Sensing Input 170~510 VAC
Can be used in Parallel Operation
16 ADC Current Output
EA16 Suitable Frequency 50/60 Hz , EA16-400Hz Suitable Frequency 400 Hz
Soft Start Voltage Ramping Load CT Current Compensation, Analogue Voltage Input
| Sensing Input | Voltage 220/380/440 VAC 1 phase 2 wire DIP switch selectable |
| Frequency 50/60 Hz DIP switch selectable | |
| Power Input | Voltage 100~300 VAC 1 phase 2 wire |
| Output | Voltage Max. 63 VDC @ 220 VAC input |
| Max. 90 VDC @ 240 VAC input | |
| Current Continuous 5A, Intermittent 7A for 10 sec | |
| Resistance Min. 15 Ohm Max. 100 Ohm | |
| Volts Regulation | < ±0.5% |
| Voltage Build-up | Residual volts at AVR terminal > 5 VAC |
| External Volts Adjustment | 7% with 1 K Ohm 1 watt trimmer |
| Unit Power Dissipation | Max. 8 watt |
| Soft Start Ramp Time | 3 sec |
| Thermal Drift | 0.03% per °C change in AVR ambient |
| Under Frequency Protection | 60 Hz system presets knee point at 55 Hz |
| 50 Hz system presets knee point at 45 Hz | |
| Environment | Operating Temperature : -40~70 °C |
| Storage Temperature : -40~85 °C | |
| Relative Humidity : Maximum 95% | |
| Vibration: 3G @ 100~2 KHz | |
| Dimensions | 101.0 (L) x 69.0 (W) x 49.5 (H) mm |
| Weight | 183g ±2% |